Code Name Rang Factory
Default
Description
G. COM Communication parameter set
COMM Communication methods OFF, RO, R-W R-W
(8)
ADDR Local address 1 ~ 255 1
BAUD Baud rate 2.4k, 4.8k, 9.6k, 19.2k, 38.4k 9.6kbps
G. RET Variable feed output parameter set
RTYP Variable output type
A output: 4 – 20mA DC
0 – 20mA DC
0 – 10mA DC
4 – 20mA DC
The output current signal is
proportional to the change
in the measured value
V output: 0 – 10V DC
0 – 5V DC
1 – 5V DC
0 – 10V DC
The output current signal is
proportional to the change
in the measured value
RETH Transmission upper limit
-1999 ~ 9999 (GW621 / GW626)
-199999 ~ 999999 (GW631 / GW636)
1000
Measured value is
corresponding to the output
of 20mADC
RETL Transmission lower limit
-1999 ~ 9999 (GW621 / GW626)
-199999 ~ 999999 (GW631 / GW636)
0
Measured value is
corresponding to the output
of 4mADC
(1) Display update cycle: when the measured value changes rapidly, increasing the display update
cycle can improve the readability of the display.
(2) ALT1, ALT2 Alarm type: HI upper limit alarm, LO lower limit alarm.
ALY1 and ALY2 alarm action error: when the measured value is near the alarm value, repeated
actions often occur in the alarm output due to input fluctuations and other reasons. Setting
appropriate alarm action error can prevent repeated actions of the alarm output.
Start delay time for ALN1 and ALN2 alarm, and close delay time for ALF1 and ALF2 alarm:
when the measured value reaches the alarm action value, move after the delay time. If the
measured value changes during the delay and the action condition is no longer met, there is no
alarm action.