EasyManuals Logo

Kidde Fire Systems FM-200 ECS Series User Manual

Default Icon
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
4-6
90-FM200M-000 September 2004
FM-200
®
ECS Series Engineered Fire Suppression Systems
4-2.3.1 FIRST BRANCH FLOW SPLIT
To assure accuracy of the flow calculations, there are
various agent flow limits. The maximum % agent in pipe
for all systems is 80%. There is a limit on the allowable
percent of agent prior to the first tee. When these condi-
tions are not met, the computer displays a warning. It is
then up to the system designer to correct the piping vol-
ume to the first branch split. For example, when reading
Figure 4-1, in order to achieve 60% agent in pipe, a mini-
mum of 8.3% agent is required prior to the first tee. When
this condition is not met, the computer displays a warn-
ing. It is then up to the system designer to correct the
piping volume to the first branch split to meet this design
requirement (see Figure 4-2).
Limits: % of agent in pipe and % of agent
before first tee. (As computed by "FLOW",
do not use for manual computation.)
7.9%
8.3%
33.6%
0%
5%
10%
15%
20%
25%
30%
35%
0% 10% 20% 30% 40% 50% 60% 70% 80%
% OF AGENT IN PIPE
% OF AGENT BEFORE
FIRST TEE
Figure 4-1. Percent Agent Before First Tee as a
Function of Percent Agent in Pipe
4-2.3.2 TEE FLOW SPLITS
Flow splits at tee junctions are sensitive to gravity. Even
though turbulent flow exists, there is a tendency for the va-
por phase to migrate to the upper portion of the pipe leav-
ing a more dense medium at the bottom of the pipe. For
this reason, the limitations in Figure 4-2 must be observed.
4-2.3.2.1 Requirements for Tee Flow Splits
1. Bull head tees must have both outlets in the horizontal
plane. The inlet to a bull head tee may approach in a
horizontal, vertically up or vertically down direction.
2. Side tees must have the inlet and both outlets all in the
horizontal plane.
3. Elbows either before a tee, or after, which split to a
separate hazard must be located a minimum distance
of 15 pipe diameters (nominal) before the tee.
4. Tee splits going to separate hazards from a common
supply line must be spaced a minimum of 15 pipe di-
ameters (nominal) apart.
5. Pipe reducers must be the concentric reducer type.
6. Minimum flow out of a side tee branch is 10% of total
flow at the tee.
7. For flow splits less than 30%, the split shall be done
through a side tee with the smaller flow going through
the side tee member. The minimum flow through the
side tee member is 10%. The maximum flow through
the tee is 90%.
8. For flow splits equal to or greater than 30%, the split
shall be done through a bull head tee. The maximum
flow split through a bull head tee is 70%.
Table 4-5. 15 Pipe Diameters
Pipe Size
15 Pipe Diameters
feet
feet and
inches
meters
1/2"
0.63 0.192
3/4"
0.94 1 0.287
1"
1.25 1'3" 0.381
"
1.56 1'6¾" 0.475
"
1.88 1'10½" 0.573
2"
2.50 2'6" 0.762
2½"
3.13 3'1½" 0.954
3"
3.75 3'9" 1.143
4"
5.00 5' 1.524

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde Fire Systems FM-200 ECS Series and is the answer not in the manual?

Kidde Fire Systems FM-200 ECS Series Specifications

General IconGeneral
BrandKidde Fire Systems
ModelFM-200 ECS Series
CategoryFirefighting Equipment
LanguageEnglish

Related product manuals