Fire Sentry
Battery Operated 4” Smoke Alarm
Model i9040
Technical Specifications
Model Number: i9040
Power Source: 9V Battery (included)
Audio Alarm: 85dB at 10ft
Temperature Range: 40˚F to 100˚F (4°C to 38°C)
Humidity Range: up to 85% relative humidity (RH)
Sensor: Ionization
Size: 4” in diameter x 1.45” depth
Weight: .5lbs
Interconnects: No
Warranty: 3 year limited
**Not for sale by individual unit
Ordering Pack Pack Dimensions Case Casesper
Number UPC I2of5 Confg. Quantity (wxdxhinches) Weight pallet
0914 0-25417--00914-9 200-25417-00914-3 BOX Cut Case (12 Units) 6.60 x 13.00 x 4.60 4.55 lbs 168
0914-9960 0-25417--91460-3 200-25417-91460-7 BOX Cut Case (8 Units) 10.30 x 10.70 x 7.60 7.30 lbs 84
0914-040 0-25417--91422-1 300-25417-91422-2 BOX Cut Case (40 Units) 9.00 x 17.00 x 9.00 15.00 lbs 30
0914T-020 0-25417--91422-1 200-25417-91422-5 BOX Cut Case (20 Twin Packs) 9.00 x 17.00 x 9.00 15.00 lbs 60
0914E 0-25417--09145-8 200-25417-09145-2 BOX Master Pack (12 Units) 10.10 x 10.10 x 5.10 5.20 lbs 112
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.kidde.com
Distributed by:
KL-i9040 sheet Rev. 1-12-09
Architectural and Engineering
Specifications
The smoke alarm shall be Kidde Model Number i9040
or approved equal. It shall be powered by a 9V battery.
The unit shall incorporate an ionization smoke sensor
with nominal sensitivity of 0.52-1.12%/ft. The tempera-
ture operating range shall be between 40°F and 100°F
(4°C and 38°C) and the humidity operating range shall
be up to 85% relative humidity.
The alarm can be installed on the surface of any wall
or ceiling following the UL/NFPA/Manufacturer’s recom-
mended placement guidelines.
The alarm shall include a test button that will electroni-
cally simulate the presence of smoke an cause the unit
go into alarm. This sequence tests the unit’s electronics,
battery and horn to ensure proper operation.
The unit shall include a piezoelectric horn that is rated
at 85 decibels at 10 feet. The alarm shall produce the
ANSI S3.41 three pulse temporal pattern audible emer-
gency evacuation signal.
The unit shall also indicate a low battery warning utiliz-
ing a brief alarm chirp ever 30-40 seconds for a minimum
of seven (7) days.
The smoke alarm shall at a minimum meet the require-
ments of UL 217, NFPA 72, The California State Fire
Marshall, NFPA 101 (One and two family dwellings
Federal Housing Authority (FHA). It shall also include a
3-year manufacturer’s limited warranty.
Ordering Information
Includes 9V Carbon Zinc Battery

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde FIRE SENTRY i9040 and is the answer not in the manual?

Kidde FIRE SENTRY i9040 Specifications

Power IconPower
power source9V Battery
audio alarm85dB at 10ft
Operating Environment IconOperating Environment
temperature range40°F to 100°F (4°C to 38°C)
humidity rangeup to 85% relative humidity
Weight and Dimensions IconWeight and Dimensions
size4” in diameter x 1.45” depth
weight0.5 lbs