EasyManua.ls Logo

Kidde KN-COPP-3 - Specifications

Kidde KN-COPP-3
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
Specifications
Power:
120 V AC units: 60 Hz, Current 60 mA max.
Sensor:
Sensor calibrated at 150 ppm (±25 ppm).
Temperature:
Operating range: 4.4˚C (40˚F) to 37.8˚C (100˚F).
Humidity:
Operating range: 5–95% non-condensing.
Mounting:
Accessories supplied for wall mount, direct plug and tabletop
applications.
Alarm:
85+ dB at 3 m (10') @ 3.4 ± 0.5 KHz pulsing alarm.
CO Alarm Time:
At 70 PPM, the unit must alarm within 60–240 minutes.
At 150 PPM, the unit must alarm within 10–50 minutes.
At 400 PPM, the unit must alarm within 4–15 minutes.
Digital Display Accuracy:
Each Kidde CO Alarm is calibrated at a CO concentration
of 150 ppm in air, at 80˚ F (+/- 10˚ F). Depending on the
ambient condition (temperature, humidity) and the
condition of the sensor, the alarm readings may vary.
The digital reading tolerances are:
Ambient: 80˚ F (+/- 10˚ F), atmospheric pressure +/- 10%,
40% +/- 3% relative humidity.
Tolerance
Reading (of displayed reading)
0-999 ppm +/-20% +15 ppm
Depending on the ambient condition (temperature,
humidity) and the condition of the sensor, the alarm
readings may vary.

Other manuals for Kidde KN-COPP-3

Related product manuals