Datasheet 3.50-32.016-01-EN
DSY/4..32
Issue 2011-05-04
A
Änderungen vorbehalten - Contents subject to change - Sous réserve de modifications - Reservado el derecho a modificación - Wijzigingen
voorbehouden - Con riserva di modifiche - Innehåll som skall ändras - Změny vyhrazeny - Zmiany zastrzeżone - Возможны изменения
-
A változtatások jogát fenntartjuk -
保留未经通知而改动的权力
Product Description
DSY/4..32 Actuating Drives
Application
DSY/4, DSY/8, DSY/16, DSY/24 and DSY/32 actuating drives with
continuous control are used to control air dampers in VAC systems.
The drives are equipped with a universal adapter and are mounted
directly on the air damper axle.
Content Page
Important Information Regarding Product Safety ..................................................................................................2
Item........................................................................................................................................................................3
Technical Data.....................................................................................................................................................3
Accessories .........................................................................................................................................................3
Dimensions..........................................................................................................................................................4
Connection...........................................................................................................................................................4
Mounting and Installation.......................................................................................................................................5
Commissioning ......................................................................................................................................................6
Setting rotational direction and rotational angle limitation DSY/4 ........................................................................6
Setting rotational direction DSY/8..32..................................................................................................................7
Rotational angle limitation DSY/8..32 ..................................................................................................................9
DSY/8..32/E auxiliary switch setting ..................................................................................................................10
Question and Answer IconNeed help?

Do you have a question about the Kieback&Peter DSY/4 and is the answer not in the manual?

Overview

The DSY/4..32 series comprises actuating drives designed for continuous control of air dampers in HVAC systems. These drives are equipped with a universal adapter for direct mounting on the air damper axle. The series includes models DSY/4, DSY/8, DSY/16, DSY/24, and DSY/32, with the DSY/8..32/E models featuring two adjustable auxiliary switches.

Function Description

The DSY/4..32 actuating drives are designed to precisely control air dampers. They receive a continuous control signal (Y) and translate it into a rotational angle to position the damper. The rotational direction can be reversed, and the rotational angle can be limited, offering flexibility in application. The DSY/8..32/E models extend functionality by incorporating two adjustable auxiliary switches, which can be set to trigger at specific rotational angles, enabling additional control or feedback within the HVAC system.

Important Technical Specifications

  • Nominal Voltage: 24 V AC ±20% or 24 V DC ±10%.
  • Power Consumption:
    • In operation: DSY/4 = 2.5 W; DSY/8..32 = 2.5 W.
    • In end position: DSY/4 = 0.75 W; DSY/8..32 = 0.3 W.
  • Control Signal (Y):
    • DSY/4: DC 0 to 10 V (Ri > 100 kΩ).
    • DSY/8..32: DC 0 to 10 V (Ri > 250 kΩ) or 0 to 20 mA (Ri 388 Ω).
  • Position Indication: Scale on actuating drive plus position feedback 0..10 V DC (R >= 50 kΩ).
  • Torque:
    • DSY/4: 4 Nm (for damper surface area up to 0.8 m²).
    • DSY/8: 8 Nm (for damper surface area up to 2 m²).
    • DSY/16: 16 Nm (for damper surface area up to 4 m²).
    • DSY/24: 24 Nm (for damper surface area up to 6 m²).
    • DSY/32: 32 Nm (for damper surface area up to 8 m²).
  • Rotational Angle:
    • Working range: 0 to 90°, invertible rotational direction.
    • DSY/4: Limitation possible at 0 to 30° and 60 to 90°.
    • DSY/8..32: Limitation possible from 5° to 85° in 5° increments.
  • Run Time (for 90° rotational angle):
    • DSY/4: 35 s.
    • DSY/8: 30 s.
    • DSY/16: 80 s.
    • DSY/24: 125 s.
    • DSY/32: 200 s.
  • Auxiliary Switches (DSY/8..32/E): Two adjustable auxiliary switches, 24 V AC, 3 (1.5) A. Delivery setting: 10° and 80° rotational angle.
  • Degree of Protection:
    • DSY/4: IP42 (IP44 with M16 x 1.5 screw fittings).
    • DSY/8..32: IP54 (cable at the bottom).
  • Ambient Temperature: -20 °C to +50 °C.
  • Ambient Humidity: 5% to 95% r.h., non-condensing.
  • Weight: DSY/4 0.9 kg; DSY/8..32 1.1 kg.

Usage Features

The DSY/4..32 drives offer several features for flexible and precise control:

  • Universal Adapter: Facilitates direct mounting on the air damper axle, simplifying installation.
  • Adjustable Control Signal Input: For DSY/8..32 models, adjusters O (starting point) and S (working range) allow modification of the Y control signal input, enabling fine-tuning to specific system requirements.
  • Automatic Adaptation: Double switch A (Switch 1) on DSY/8..32 models allows for automatic adaptation of the control signal Y to the mechanical rotational angle. When set to ON, the drive performs an initialization run, automatically approaching both end positions. This feature ensures that the control signal is adjusted to the available rotational angle, even if it changes or is limited.
  • Reversible Rotational Direction: Double switch A (Switch 2) allows for easy reversal of the rotational direction, providing adaptability to different damper configurations.
  • Mechanical Rotational Angle Limitation:
    • DSY/4: Features left and right stops for mechanical limitation of the rotational angle, adjustable from 0° to 30°. These screws can reduce the 90° working range by 30° from each end position.
    • DSY/8..32: The adapter can be reinserted to limit the rotational angle, allowing for a working range from 5° to 85° in 5° increments. This is achieved by disengaging retaining clips, pulling out the adapter, and reinserting it at the desired end position.
  • Manual Adjustment: A sliding switch on the DSY/4 and DSY/8..32 models allows for manual adjustment of the damper position.
  • Auxiliary Switches (DSY/8..32/E): Two adjustable auxiliary switches can be set to trigger at specific rotational angles (e.g., 10° and 80° as a delivery setting). These can be configured by moving the sliding switch for manual adjustment and turning ratchet wheels D1 and D2 until microswitches E1 and E2 switch, respectively.

Maintenance Features

  • Safety First: The manual emphasizes the importance of disconnecting the actuator from power before mounting, removing, or performing any maintenance to prevent electric shock. This includes removing the cover for internal adjustments.
  • Clear Instructions: Detailed instructions are provided for setting rotational direction and rotational angle limitation, which are crucial for proper device operation and can be considered part of routine setup or recalibration.
  • Accessible Components: Internal components like connection terminals, adjusters, and switches are accessible once the cover is removed, facilitating adjustments and troubleshooting.
  • VDE Guidelines Compliance: Users are instructed to comply with VDE guidelines and local wiring regulations during mounting and removal, ensuring safe and compliant maintenance practices.

Kieback&Peter DSY/4 Specifications

General IconGeneral
BrandKieback&Peter
ModelDSY/4
CategoryDC Drives
LanguageEnglish