STE-9000 Series NetSensors
Installation Guide
NOTE: The hex screw
2
should remain in the
backplate.
2
2. Pull the cover from the backplate.
CONNECT ETHERNET CABLE
3. Feed the Ethernet patch cable
3
from the
Conquest controller through the center of the
backplate
4
.
NOTE: The Ethernet patch cable should be a
maximum of 150 feet (45 meters).
3
4
4. Mount the backplate on an electrical box using the
screws provided.
NOTE: If additional thermal insulation is needed,
install the optional HPO-9002 gasket
between the backplate and the electrical
box. For more information, see the Room
Sensor and Thermostat Mounting Location
and Maintenance Application Guide.
INTRODUCTION
Complete the following steps to mount a KMC Conquest
STE-9000 Series Digital NetSensor and connect it to a
Conquest BAC-59xx/9xxx Controller.
STE-90xx/93xx
STE-9xxxW-NDL
(no display)
NOTE: See the Conquest NetSensors STE-9000
Series Digital Room Sensors data sheet
and the Conquest Selection Guide at
kmccontrols.com for specifications and
other information.
SELECT MOUNTING LOCATION
See the Room Sensor and Thermostat Mounting
Location and Maintenance Application Guide for
cautions, troubleshooting, and best practices.
NOTE: Complete rough-in-wiring at each location
before installing a sensor.
REMOVE BACKPLATE
1. Turn the hex screw
1
clockwise into the sensor
until the screw clears the cover.
1
STE-92xx/95xx
with Motion Sensor