EasyManua.ls Logo

Kramer LPE

Kramer LPE
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12" 12" 12" 24" 60"
15" 15" 15" 30" 75"
18" 18" 18" 36" 90"
24" 24" 24" 48" 120"
30" 30" 30" 60" 150"
36" 36" 36" 72" 180"
42" 42" 42" 84" 210"
48" 48" 48" 96" 240"
H = Height of Evaporator
‡ Minimum walk-in height of 7'-0"
Air
Front wall
5 x H Min.
12"
Air
Product
Product Storage Area
Door
See Table above for H dimension Floor
Drawings are not to scale
No doors at side or back of evaporators. Back wall
H
H2 x H H
Side Evaporator
wall
Air Air
5 x H Side
Alternate wall
Door location
See Table above for H dimension Door Front wall
5
EVAPORATOR
HEIGHT (Key Dim.)
H
Unit to
Back Wall *
1 x H
Unit to
Side Wall
1 x H
Unit
to Unit
2 x H
LOCATING WALK-IN EVAPORATORS
MINIMUM DIMENSION FOR GOOD AIR CIRCULATION AND EVAPORATOR PERFORMANCE
60" ‡
60" ‡
Unit to
Front Wall
5 x H
Unit
to Floor
3 x H
60" ‡
72"
90"
108"
SIDE VIEW
TOP VIEW
Evaporator
126"
144"
3 x H
Evap.
Obstruction
Free
Area