Inverter output balanced by phase, limited by minimum phase power flow.
Inverter output balanced by total load, with phase-level injections or grid draw.
Instructions for releasing retaining clip and mounting the meter onto a DIN track.
Guidance on installing current transformers (CTs) with correct directionality.
Detailed diagram showing grid, meter, and inverter connections, including RS485 and PE.
Explanation of buttons (A, B, C, D) for menu navigation and selection.
Steps to configure 'Anti Rev-l' (Enable/Disable, Meter Type, Anti Method).
Instructions to set the 'Anti Amend' value for inverter output adjustment.
The KSTAR SDM630MCT 40mA is a DIN Rail Energy Meter designed for three-phase KSTAR electrical systems, offering comprehensive energy monitoring and control capabilities. This device is crucial for implementing zero export functions in KSTAR three-phase inverter systems, ensuring compliance with grid regulations and optimizing energy consumption.
The primary function of the SDM630MCT 40mA is to accurately measure various electrical parameters in a three-phase system. It provides detailed data on energy consumption and generation, which is then used by KSTAR inverters to manage power flow. The meter supports two main methods for achieving zero export:
Phase-level zero export: In this method, the inverter's three-phase outputs are balanced based on the phase with the minimum power flowing through it. For example, if the loads on phases A, B, and C are 10kW, 20kW, and 30kW respectively, the inverter will limit its output to 10kW for each phase. Any additional power required by the higher-load phases will be drawn from the grid. This ensures that no power is injected back into the grid at the individual phase level.
System-level zero export: This method balances the inverter's three-phase outputs based on the total load of the system. If the loads on phases A, B, and C are 10kW, 20kW, and 30kW respectively, the inverter's limit power for each phase will be determined by the total load, for instance, 20kW per phase. In this scenario, phases requiring less than 20kW will inject power into the grid, while phases requiring more than 20kW will draw power from the grid to meet their demand. This approach aims for overall system balance regarding grid interaction.
The meter's data-driven decisions enable the inverter to control its output effectively, preventing unwanted power export and optimizing self-consumption.
| Brand | KStar |
|---|---|
| Model | EASTRON SDM630MCT 40mA |
| Category | Measuring Instruments |
| Language | English |