EasyManuals Logo

Lennox DM User Manual

Lennox DM
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
DC-DM-ROOFTOP-IOM-1801-E - 49 -
CODE DESCRIPTION CONDITION EFFECT RESET POSSIBLE CAUSES POSSIBLE REMEDIES
DS
MENU
328
Circuit 3 Compressor, LOP
operating, (Low Operating
Press.).
The suction temperature
calculated by the LP pressure
sensor is outside of the
permitted range.
Threshold: (HP < 35°C) < -
25°C,
Threshold: (HP < 55°C) < -C,
Threshold: (HP > 65°C) <
12.5°C,
Delayed: 1min,
Enabled: 3min after one
compressor or condenser fan
start/stop.
Signalling. Automatic
• Limit indoor/outdoor
temperature conditions,
• Refrigerant charge,
• Problem with the expansion
valve.
• Wait normal tempetaure
conditions,
• Check the circuit operating,
• Replace the expansion valve.
#
329
Circuit 3 Compressor,
Condensing T°, Too High.
The temperature measured by
the probe is outside of the
permitted range.
Threshold: > 61°C,
Delayed: 20s,
Waiting stop: 6min,
Enabled: 3min after one
compressor or condenser fan
start/stop.
Signalling. Automatic
• Limit indoor/outdoor
temperature conditions,
• Refrigerant charge,
Problem with the expansion
valve.
• Wait normal tempetaure
conditions,
• Check the circuit operating,
• Replace the expansion valve.
#
341
Faulty Sensor.
The value of the sensor
Delayed: 15s.
Stop C3
compressors.
Automatic
• Sensor failure,
• Problem with wiring of sensor.
• Check the sensor
• Check the wiring connections.
#
342
Faulty Sensor.
The value of the sensor
Delayed: 15s.
Stop C3
compressors.
Automatic
• Sensor failure,
• Problem with wiring of sensor.
• Check the sensor
• Check the wiring connections.
#
343
Temperature, Probe.
The value of the sensor
Delayed: 15s.
Stop C3
compressors.
Automatic
• Probe failure,
• Problem with wiring of probe.
• Check the probe
• Check the wiring connections.
#
344
The value of the sensor
Delayed: 15s.
Stop C3
compressors.
Automatic
• Probe failure,
• Problem with wiring of probe.
• Check the probe
• Check the wiring connections.
#