CAUTION
5.1 Outdoor Unit Wiring
10
Equipment complying with IEC 61000-3-12.
A disconnection device having an air gap contact separation
in all active conductors should be incorporated in the fixed
wiring according to the National Wiring Regulation.
The reserved function is indicated in broken line table,users
can select it when necessary.
CAUTION
Indoor/Outdoor Unit Signal Wire
Connect the wire according to their numbers.
Fig. 5-2
Wiring the indoor unit and outdoor unit control
P Q EP Q E P Q E P Q E
P QE
Note: The parts in the dotted line box are optional.Contact
the local distributor to purchase them if required.
Outdoor
unit
Indoor unit Indoor unit Indoor unit Indoor unit
Wired
controller
Remote
control
Add a build-out resistor
at the P/Q end of the last
indoor unit only.
Build-out
resistor
Use a shield cable and
ground the shielding layer.
When the power cable is parallel to the signal cable, insert electric wires in their respective electric wire pipes
and reserve a proper inter-wire distance. (distance between power cables: lower than 10 A –300 mm; lower
than 50 A – 500 mm)
Use a three-core shielded cable as the indoor/outdoor unit signal cable, and ground the shielding layer as
required.
The display box, remote control, and build-out resistor are accessories for the indoor unit. The wired controller
is optional. To purchase a wired controller, contact your local distributor.
The Specification of Power
Functions of Outdoor Unit Wiring Terminals
Table 5-1
A
B
N
C
Power Supply
XT2
K1 K2 E O A E
X Y E P Q E
Indoor and outdoor
unit communication
Outdoor unit
monitor
Central indoor
unit controller
Digital
ammeter
Note:Use a three-core shielded cable,
and ground the shielding layer
Fig. 5-3
26
50/60
380-415
342
456
26.25
23
32
/
15.4
2×0.17
2.1+1.7
22.4
50/60
380-415
342
456
25
23
25
/
15.4
2×0.17
2.1+1.7
20
50/60
380-415
342
456
18.75
18
25
/
12
2×0.17
2.1+1.7
Model
Capicity(kW)
Hz
Voltage
Min.(V)
Max.(V)
MCA
TOCA
MFA
MSC
RLA
kW
FLA
380-415V 3Ph~ 50Hz/60Hz
Power
Supply
Compressor
OFM
Power Source