Switch 5 −− Cooling Blower−Off Delay −− The cooling
blower−off delay (time that the blower operates after the
cooling demand has been satisfied) can be adjusted by
moving switch 5 on the integrated control. The switch is fac-
tory−set in the OFF position, which provides a cooling blow-
er−off delay of 45 seconds. If the switch is toggled to the ON
position, it will provide a 2−second cooling blower−off delay
On−Board Link W951 Heat Pump (R to O)
On−board link W951 is a clippable connection between ter-
minals R and O on the integrated control. W951 must be cut
when the furnace is installed in applications which include a
heat pump unit and a thermostat which features dual fuel
use. If the link is left intact, terminal O" will remain ener-
gized eliminating the HEAT MODE in the heat pump.
On−Board Link W915 2 Stage Compr (Y1 to Y2)
On−board link W915 is a clippable connection between ter-
minals Y1 and Y2 on the integrated control. W915 must be
cut if two−stage cooling will be used. If the Y1 to Y2 link is
not cut the outdoor unit will operate in second−stage cooling
only.
TWO−STAGE INTEGRATED CONTROL
THERMOSTAT CONNECTIONS (TB1)
1/4" QUICK CONNECT TERMINALS
DIP SWITCH FUNCTIONS
DIP
SWITCHES
DIAGNOSTIC
LEDs
ON−BOARD
LINKS
1= ERROR CODE RECALL
H= 24V HUMIDIFIER OUTPUT
L= LENNOX SYSTEM OPERATION MONITOR
SENSE = 120 VAC OUTPUT TO FLAME SENSOR
NEUTRALS= 120 VAC NEUTRAL
PARK = DEAD TERMINAL FOR UNUSED BLOWER LEAD
HEAT LOW = 120 VAC OUTPUT TO CIRC BLWR −− LOW HT SPEED & CONT FAN
HEAT HIGH/ COOL LOW = 120 VAC OUTPUT TO CIRC BLWR −−
HIGH HEAT AND LOW COOL SPEED
COOL HIGH = 120 VAC OUTPUT TO CIRC BLWR −− HIGH COOL SPEED
DIP SWITCH(ES) FUNCTION
1 −− 2 Stage T’stat Selects t/stat type (single or two−stage)
2 −− 2nd Stage Delay Second stage ON delay (single−stage t’stat)
3 & 4 −− Heat Off Delay Heating fan OFF delay
5 −− Cool Off Delay Cooling fan OFF delay
W915
W951
FIGURE 5
TABLE 2
SureLight control 5 Pin Terminal Designation
PIN # Function
1 Ignitor
2 Combustion Air Inducer High Speed
3 Combustion Air Inducer Low Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
TABLE 3
SureLight control 12Pin Terminal Designation
PIN # Function
1 Gas Valve High Fire
2 Second Stage pressure Switch
3 Rollout In
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve Low Stage
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Rollout Switch Out
12 1st Stage pressure Switch