Page 27
Gas  supply  piping  should  not  allow  more  than  0.5”W.C. 
drop in pressure between gas meter and unit. Supply gas 
pipe must not be smaller than unit gas connection. Com-
pounds used on gas piping threaded joints should be re-
sistant to action of liqueed petroleum gases.
C-Testing Gas Piping
 WARNING
In  case  emergency  shutdown  is  required,  turn  o 
the  main  shut-o  valve  and  disconnect  the  main 
power to unit. These controls should be properly 
labeled by the installer.
When pressure testing gas lines, the  gas  valve must be 
disconnected and isolated. Gas valves can be damaged if 
subjected to more than 0.5 psig (14” W.C.). See FIGURE 
20. If the pressure is greater than 0.5psig (14”W.C.), use 
the manual shut-o valve before pressure testing to iso-
late furnace from gas supply.
MANUAL MAIN SHUT-OFF VALVE
WILL NOT HOLD TEST PRESSURE
IN EXCESS OF 0.5 PSIG (14”W.C.)
GAS VALVE
CAP
GAS PIPING TEST PROCEDURE
FIELD PROVIDED
1/8 NPT PLUG
FIGURE 20 
When  checking  piping  connections  for  gas  leaks,  use 
preferred  means.  Kitchen  detergents  can  cause  harmful 
corrosion on various metals used in gas piping. Use of a 
specialty Gas Leak Detector is strongly recommended. It 
is available through Lennox under part number 31B2001. 
See Corp. 8411-L10, for further details.
Do  not  use  matches,  candles,  ame  or  any  other 
source of ignition to check for gas leaks.
D-Testing Gas Supply Pressure
A threaded plug on the inlet side of the gas valve provides 
access  to  the  supply  pressure  tap.  Remove  the  thread-
ed plug, install a eld-provided barbed tting and connect 
a manometer to measure supply pressure. See table 14 
for supply line pressure. Replace the threaded plug after 
measurements have been taken.
E-Check Manifold Pressure
After line pressure has been checked and adjusted, check 
manifold pressure. Checks of manifold pressure are made 
as  verication  of  proper  regulator  adjustment.  Manifold 
pressure for the EL280UHE(X)  can be measured at any 
time the gas valve is open and is supplying gas to the unit.
 IMPORTANT
For  safety,  connect  a  shut-o  valve  between  the 
manometer and the gas tap to permit shut o of gas 
pressure to the manometer.
The gas valve is factory set and should not require adjust-
ment. All gas valves are factory regulated.
Manifold Adjustment Procedure:
NOTE - Pressure test adapter kit (10L34) is available from 
Lennox to facilitate manifold pressure measurement.
1 -   Connect  test  gauge  to  manifold  pressure  post 
(FIGURE 19) on gas valve.
2 -   Ignite unit  on low  re  and  let  run for  5 minutes  to 
allow for steady state conditions.
3 -   After allowing unit to stabilize for 5 minutes, record 
manifold  pressure  and  compare  to  value  given  in 
table 14.
4 -   If  necessary,  make  adjustments.  Figure  18  show 
location of high re and low re adjustment screw.
5 -  Repeat steps 2, 3 and 4 on high re.
6 -   Shut unit o and remove manometer as soon as an 
accurate reading has been obtained. Take care  to 
replace pressure tap plug.
7 -   Start  unit  and  perform  leak  check.  Seal  leaks  if 
found.
F- Proper Gas Flow (Approximate)
Furnace should operate at least 5 minutes before check-
ing  gas  ow.  Determine  time  in  seconds  for  two  revolu-
tions of gas through the meter. (Two revolutions assures 
a more accurate time.) Divide by two and compare to time 
in TABLE 12 below. If manifold pressure matches TABLE 
14 and rate is incorrect, check gas orices for proper size 
and restriction.
NOTE- To obtain accurate reading, shut o all other gas 
appliances connected to meter.
TABLE 12 
GAS METERING CLOCKING CHART
Input
Natural 1000 btu/
cu ft
LP 2500 btu/cu ft
Seconds For One Revolution
1 cu ft 
dial
2 cu fr 
dial
1 cu ft 
Dial
2 cu ft 
Dial
-045 80 160 200 400
-070 55 110 136 272
-090 41 82 102 204
-110 33 66 82 164
 IMPORTANT
For safety, shut unit o and remove manometer as 
soon as an accurate reading has been obtained. 
Take care to replace pressure tap plug.