7. Combustion Air Inducer (B6) and
Cold End Header Box
All EL296DFV(X) units use a two-stage combustion air in-
ducer to move air through the burners and heat exchanger 
during heating operation. The blower uses a 120VAC mo-
tor. The motor operates during all heating operation and 
is controlled by integrated control A92. The  inducer  also 
operates for 15 seconds before burner ignition (prepurge) 
and for 5 seconds after the gas valve closes (postpurge). 
The inducer operates on low speed during rst stage heat, 
then switches to high speed for second stage heat.
NOTE - Each furnace model uses a unique CAI. Refer to 
Lennox Repair Parts listing for correct inducer for replace-
ment.
The  combustion  air  inducer  is  installed  on  the  cold  end 
header  box.  The  cold  end  header  box  is  a  single  piece 
made  of  hard  plastic.  The  box  has  an  internal  channel 
where the combustion air inducer creates negative pres-
sure at unit start up. The channel contains an orice used 
to regulate ow created by the combustion air inducer.
The box has pressure taps for the combustion air induc-
er pressure switch hoses. The pressure switch measures 
the pressure dierential across the combustion air inducer 
orice or dierence in the channel and the box. If replace-
ment is necessary the gaskets used to seal the box to 
the vestibule panel and the combustion air inducer to 
the box, must also be replaced.
A proving switch connected to the combustion air inducer 
orice plate is used to prove inducer operation. The com-
bustion air inducer orice will be dierent for each model. 
See TABLE 16 for orice sizes. The pressure switch mea-
sures the pressure dierential across the combustion air 
inducer  orice. When  the  proving  switch opens,  the  fur-
nace  control  (A92)  immediately  closes  the  gas  valve  to 
prevent burner operation.
TABLE 16 
EL296DFV Unit C.A.I. Orice Size
-045 0.618
-070 0.810
-090 0.920
-110 1.040
8. Combustion Air Inducer
Pressure Switch (S18)
EL296DFV(X) series units are equipped with a dual com-
bustion  air  pressure  switch  (rst  and  second  stage)  lo-
cated on the combustion air inducer orice bracket. See 
FIGURE 16. The switch is  connected  to the combustion 
air inducer housing by means of a exible silicone hose. 
It monitors negative air pressure in the combustion air in-
ducer housing.
The  switches  are  a  single-pole  single-throw  pressure 
switch electrically connected to the integrated control. The 
purpose of the switch is to prevent burner operation if the 
combustion air inducer is not operating or if the ue be-
comes obstructed.
On heat demand (rst or second stage) the switch senses 
that  the  combustion  air  inducer  is  operating.  It  closes  a 
circuit to the integrated control when pressure inside the 
combustion air  inducer decreases to  a certain set  point. 
Set  points  vary  depending  on  unit  size.  See  TABLE  17. 
The  pressure  sensed  by  the  switch  is  negative  relative 
to atmospheric pressure. If the  ue  becomes obstructed 
during  operation,  the  switch  senses  a  loss  of  negative 
pressure  becomes  more  equal  with  atmospheric  pres-
sure) and opens the circuit to the furnace control and gas 
valve. A bleed port on the switch allows relatively dry air 
in the vestibule to purge switch tubing, to prevent conden-
sate build up.
COMBUSTION AIR PRESSURE SWITCH
3/16 Terminals
Low Fire Switch
High Fire Switch
1/4
" Terminals
Tap (negative - )
Tap (positive +)
FIGURE 16 
NOTE - The switch is factory  set  and is not eld adjust-
able. It  is a  safety shut-down  control in  the furnace  and 
must not be by-passed for any reason. If switch is closed 
or bypassed, the control will not initiate ignition at start up.
TABLE 17 
Unit Set Point Low Heat  Set Point High Heat
-045 0.35 0.60
-070 0.45 .090
-090 0.50 0.90
-110 0.45 0.90