Page 43
Vent Piping Guidelines
NOTE - Lennox has approved the use of DuraVent® and 
Centrotherm manufactured vent pipe and terminations as 
an option to PVC. When using the PolyPro
® 
by DuraVent 
or InnoFlue
®
 by Centrotherm venting system the vent pipe 
requirements  stated  in  the  unit  installation  instruction  – 
minimum & maximum vent lengths, termination clearanc-
es, etc. – apply and must be followed. Follow the instruc-
tions provided with PoyPro by DuraVent and InnoFlue by 
Centrotherm  venting  system  for  assembly  or  if  require-
ments are more restrictive. The PolyPro by Duravent and 
InnoFlue by Centrotherm venting system must also follow 
the uninsulated and unconditioned space criteria listed in 
table 22.
The EL296DFV can be installed as either a Non-Direct 
Vent or a Direct Vent gas central furnace.
NOTE - In Non-Direct Vent installations, combustion air is 
taken from  indoors  or ventilated  attic or crawlspace  and 
ue gases are discharged outdoors. In Direct Vent instal-
lations,  combustion  air  is  taken  from  outdoors  and  ue 
gases are discharged outdoors.
Intake and exhaust pipe sizing -- Size pipe according to 
TABLE 20 (minimum pipe lengths) and TABLE 21 (max-
immum pipe lengths). Count all elbows inside and outside 
the home.
TABLE 20 
MINIMUM VENT PIPE LENGTHS
EL296DFV MODEL MIN. VENT LENGTH*
045, 070, 090, 110
15 ft or 5ft plus 2 elbows or 
10 ft plus 1 elbow
*Any approved termination may be added to the minimum 
length listed. Two 45 degree elbows are the equivalent to 
one 90 degree elbow.
Regardless of the diameter of pipe used, the standard roof 
and wall terminations described in section Exhaust Piping 
Terminations  should  be  used.  Exhaust  vent  termination 
pipe is sized to optimize the velocity of the exhaust gas as 
it exits the termination. Refer to TABLE 24.
In some applications which permit the use of several dif-
ferent sizes of vent pipe, a combination vent pipe may be 
used. Contact Lennox’ Application Department for assis-
tance in sizing vent pipe in these applications.
 IMPORTANT
Do not use screens or perforated metal in exhaust 
or intake terminations. Doing so will cause freeze-
ups and may block the terminations.
NOTE - It  is  acceptable  to  use  any  pipe  size  which  ts 
within the guidelines allowed in TABLE 21.
NOTE - All  horizontal  runs  of  exhaust  pipe  must  slope 
backtoward unit. A minimum of 1/4” (6mm) drop for each 
12” (305mm) of horizontal run is mandatory for drainage.
NOTE - Lennox oers a glueless vent adapter kit 17H92 
as  an  option  for  exhaust  exiting  at  the  furnace  top  cap 
coupling
NOTE - Exhaust pipe MUST be glued to furnace exhaust 
ttings.
NOTE - Exhaust  piping  should  be  checked  carefully  to 
make sure there are no sags or low spots.
NOTE - If right side venting option is used, you must in-
clude the elbow at the furnace in the elbow count. If tran-
sitioning to 3” dia pipe, this elbow equates to 20’ of equiv-
alent vent length for all models.
Use the following steps to correctly size vent pipe diam-
eter.
1
2
3
4
5
6
Which style termination
being used?
Standard or concentric?
.
Which needs
most elbows?
Intake or
exhaust?
How many elbows?
Count all elbows inside
and outside house.
Desired pipe size?
What is the altitude of
the furnace installation?
7
What is the
furnace capacity?
See max and min length
tables. Include all vent pipe
and elbows inside and
outside the hpouse
FIGURE 23