Page 60
8 -  After assembly, wipe excess cement from pipe at end 
of tting socket. A properly made joint will show a 
bead  around  its  entire  perimeter.  Any  gaps  may 
indicate  an  improper  assembly  due  to  insucient 
solvent.
9 -  Handle joints carefully until completely set.
Venting Practices
* See  Piping and Fittings Specifications table
Piping Suspension Guidelines
NOTE - Isolate piping at the point where it exits the outside wall or
roof in order to prevent transmission of vibration to the structure.
SCHEDULE 40
PVC - 5'
all other pipe*  - 3'
Wall
edistuoedisni
24” maximum
3/4” minimum
Wall Thickness Guidelines
FIGURE 19 
1 -  In  areas  where  piping  penetrates  joists  or  interior 
walls, hole must be large enough to  allow  clearance 
on  all  sides  of  pipe  through  center  of  hole  using  a 
hanger.
2 -  When furnace is installed  in a residence where unit 
is shut down for an extended period of time, such 
as  a  vacation  home,  make  provisions  for  draining 
condensate collection trap and lines.
Removal of the Furnace from Common Vent
In  the  event  that  an  existing  furnace  is  removed  from  a 
venting system commonly run with separate gas applianc-
es, the venting system is likely to be too large to properly 
vent the remaining attached appliances.
Conduct the following test while each appliance is oper-
ating and the other appliances (which are not operating) 
remain connected to the common venting system. If the 
venting  system  has  been  installed  improperly,  you  must 
correct the system as indicated in the general venting re-
quirements section.
 WARNING
CARBON MONOXIDE POISONING HAZARD
Failure  to  follow  the  steps  outlined  below  for  each 
appliance connected to the venting system being placed 
into operation could result in carbon monoxide poisoning 
or death.
The following steps shall be followed for each appliance 
connected  to  the  venting  system  being  placed  into 
operation,  while  all  other  appliances  connected  to  the 
venting system are not in operation:
1 -   Seal any unused openings in the common venting 
system.
2 -  Inspect  the  venting  system  for  proper  size  and 
horizontal pitch. Determine that there is no blockage, 
restriction, leakage, corrosion, or other deciencies 
which could cause an unsafe condition.
3 -  Close all  building doors  and  windows  and  all doors 
between  the  space  in  which  the  appliances 
remaining connected to the common venting system 
are located and other spaces of the building. Turn on 
clothes dryers and any appliances not connected to 
the common venting system. Turn on any exhaust 
fans, such as range hoods and bathroom exhausts, 
so  they  will  operate  at  maximum  speed.  Do  not 
operate  a  summer  exhaust  fan.  Close  replace 
dampers.
4 -  Follow the lighting instructions. Turn on the appliance 
that  is  being  inspected.  Adjust  the  thermostat  so 
that the appliance operates continuously.
5 -  After  the  main  burner  has  operated  for  5  minutes, 
test for leaks of ue  gases at the draft hood relief 
opening. Use the ame of a match or candle.
6 -  After  determining  that  each  appliance  connected  to 
the  common  venting  system  is  venting  properly, 
(step  3  return  all  doors,  widows,  exhaust  fans, 
replace  dampers,  and  any  other  gas-burning 
appliances to their previous mode of operation.
7 -  If  a  venting  problem  is  found  during  any  of  the 
preceding tests, the common venting system must 
be modied to correct the problem.
Resize  the  common  venting  system  to  the  minimum 
vent  pipe  size  determined  by  using  the  appropriate 
tables in Appendix G. (These are in the current stan-
dards)