Page 50
NOTE - The off portion of the selected ramp prole also 
applies during  heat pump operation  in dual  fuel applica-
tions.
TABLE 14 
Cooling Mode Blower Speed Ramping
Ramping Switch 9 Switch 10
A (Factory) Off Off
B Off On
C On Off
D On On
Ramping Option A (Factory Selection)
•   Motor runs at 50% for 30 seconds.
•    Motor then runs at 82% for approximately 7-1/2 
minutes.
•   If demand has  not been satised  after 7-1/2 min-
utes, motor runs at 100% until demand is satised.
•    Once demand is met, motor runs at 50% for 30 
seconds then ramps down to stop.
OFF
1/2 MIN
50% CFM
COMPRESSOR DEMAND
7 1/2 MIN
82% CFM
100% 
CFM
1/2 MIN
50% CFM
 
Ramping Option B
•   Motor runs at 82% for approximately 7-1/2 minutes. 
If  demand  has  not  been  satised  after  7-1/2  min-
utes, motor runs at 100% until demand is satised. 
•   Once demand is met, motor ramps down to stop.
OFF
OFF
82%CFM
100% CFM
COMPRESSOR DEMAND
7 1/2 MIN
 
Ramping Option C
•    Motor runs at 100% until demand is satised.
•   Once demand is met, motor runs at 100% for 45 
seconds then ramps down to stop.
OFF
100% CFM
100% CFM
45 SEC.
COMPRESSOR
DEMAND
 
Ramping Option D
•  Motor runs at 100% until demand is satised.
•  Once demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COMPRESSOR
 DEMAND
 
Switches 11, 12 and 13 -- Heating Mode Blower Speed  
The switches are factory set to the OFF position which 
provides factory default heat speed. Refer to table 16 for 
switches 11, 12 and 13 that provided the corresponding 
increases or decrease to both high and low heat demand.
TABLE 15 
Heating Mode Blower Speeds
Heat Speed Switch 11 Switch 12 Switch 13
Increase 24% On On On
Increase 18% On On Off
Increase 12% On Off On
Increae 6% On  Off Off
Factory 
Default
Off Off Off
Decrease 6% Off Off On
Decrease 
12%
Off On Off
Decrease 
18%
Off On On
Switches 14 and 15 -- Continuous Blower Speed --
Table 17 provides continuous blower speed adjustments 
that will result from different switch settings.
TABLE 16 
Continuous Blower Speed
Coninuous Blower Speed Switch 14 Switch 15
28% of High Cool Speed Off On
38% of High Cool Speed
(Factory)
Off Off
70% of High Cool Speed On Off
100% of High Cool Speed On On