Page 62
Applications Using A Single-Stage Thermostat
See Figure 64 for ignition control sequence
B - Heating Sequence -- Integrated Control Thermostat 
Selection DIP Switch 1 ON in “Single-Stage” Position
NOTE - In these applications, two-stage heat will be initi-
ated by the integrated control if heating demand has not 
been  satised  after  the  eld  adjustable  period  (7  or  12 
minutes).
1 -   On  a  call  for  heat,  thermostat  rst-stage  contacts 
close sending a signal to the integrated control. The 
integrated control runs a self-diagnostic program 
and checks high temperature limit switches for 
normally closed contacts and pressure switches for 
normally open contacts. The combustion air inducer 
is energized at low speed.
2 -   Once the control receives a signal that the low 
pressure switch has closed, the combustion air 
inducer begins a 15-second pre-purge in low speed.
NOTE - If the low re pressure switch does not close 
the  combustion  air  inducer  will  switch  to  high  re. 
After a 15 second pre-purge the high re pressure 
switch will close and the unit will begin operation on 
high re. After 10 to 20 seconds of high re opera-
tion the unit will switch to low re.
3 -   After the pre-purge is complete, a 20-second initial 
ignitor warm-up period begins. The combustion air 
inducer continues to operate at low speed.
4 -   After the 20-second warm-up period has ended, 
the gas valve is energized  on low re  (rst stage) 
and ignition occurs. At the same time, the control 
module sends a signal to begin an indoor blower 
30-second ON-delay. When the delay ends, the 
indoor  blower  motor  is  energized  on  the  low  re 
heating speed and the HUM contacts are energized. 
The integrated control also initiates a second-stage 
on delay (factory-set at 7 minutes; adjustable to 12 
minutes).
5 -   If the heating demand continues beyond the 
secondstage on delay, the integrated control 
energizes the combustion air inducer at high speed. 
The control also checks the high re (second stage) 
pressure switch to make sure it is closed. The high 
re (second stage) gas valve is energized and the 
indoor blower motor is energized for operation at 
the high re heating speed.
6 -   When the  thermostat heating  demand is  satised, 
the combustion air inducer begins a 5-second low 
speed post-purge. The eld-selected indoor blower 
off delay begins. The indoor blower operates at the 
low-re heating speed.
7 -   When the combustion air post-purge period is 
complete, the inducer and the HUM contacts are 
de-energized. The indoor blower is de-energized at 
the end of the off delay as well as the 120V ACC 
terminals.
1 stg heat demand
2 stg heat demand
15
ON
OFF
low speed CAI
35
1
Pre-Purge
Ignitor Warm-up
30* second
blower
“on” delay
Post
 Purge
5 SEC80
ignitor
HEATING OPERATION WITH TWO-STAGE THERMOSTAT
low fire gas valve
indoor blower low heat
high speed CAI
high fire gas valve
indoor blower high heat
39
Trial For
Ignition
blower
“off”
delay
 RECOGNITION PERIOD
30 seconds
* Conventional thermostat 30 seconds, icomfort Touch
®
 thermostat set for 30 adjustable 15 to 45 seconds.
Figure 63 
heat demand
15
ON
OFF
low speed CAI
35
1
Pre-Purge
Ignitor Warm-up
30* second
blower
“on” delay
Post
 Purge
5 SEC
80
ignitor
HEATING OPERATION WITH SINGLE STAGE THERMOSTAT
low fire gas valve
high speed CAI
high fire gas valve
indoor blower high heat
39
Trial For
Ignition
7 or 12 minutes after heating demand begins, furnace switches to high fire (depends on setting)
blowe
“off”
delay
indoor blower low heat
* Conventional thermostat 30 seconds, icomfort Touch
®
 
thermostat set for 30 adjustable 15 to 45 seconds.
Figure 64