Page 33
TABLE 5 
 Ignition Control 103130-XX Diagnostic Codes
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
. Idle mode (Decimal blinks at 1 Hertz -- 0.5 
second ON, 0.5 second OFF).
A Cubic feet per minute (cfm) setting for 
indoor blower (1 second ON, 0.5 second 
OFF) / cfm setting for current mode 
displayed.
C Cooling stage (1 second ON, 0.5 second 
OFF) / 1 or 2 displayed / Pause / cfm 
setting displayed / Pause / Repeat codes).
d Dehumidication mode (1 second ON) / 
1 second OFF) / cfm setting displayed / 
Pause / Repeat Codes).
h Heat pump stage (1 second ON, 0.5 
second OFF) / % of input rate displayed 
/ Pause / cfm setting / Pause / Repeat 
codes.
H Gas Heat Stage (1 second ON, 0.5 second 
OFF) / 1 or 2 displayed / Pause / cfm 
setting displayed / Pause / Repeat codes. 
Blinking during ignition.
dF Defrost mode.
U Discharge Air Temperature
E105 Device communication problem - No other 
devices on RS BUS (Communication 
system).
Equipment is unable to communicate. Indicates numerous message 
errors. In most cases errors are related to electrical noise. Make sure 
high voltage power is separated from RSBus. Check for miswired and/or 
loose connections between the stat, indoor unit and outdoor unit. Check 
for a high voltage source of noise close to the system. Fault clears after 
communication is restored.
E110 Low line voltage. Line Voltage Low (Voltage lower than nameplate rating). Check power line 
voltage and correct. Alarm clears 5 seconds after fault recovered.
E111 Low line voltage. Reverse line power voltage wiring. System resumes normal operation 5 
seconds after fault recovered.
E112 Ground not detected System shuts down. Provide proper earth ground. System resumes normal 
operation 5 seconds after fault recovered.
E113 High line voltage. Line Voltage High (Voltage higher than nameplate rating). Provide power 
voltage within proper range. System resumes normal operation 5 seconds 
after fault recovered.
E114 Line voltage frequency out-of-range. No 60 Hertz Power. Check voltage and line power frequency. Correct 
voltage and frequency problems. System resumes normal operation 5 
seconds after fault recovered.
E115 Low 24V - Control will restart if the error 
recovers.
24-Volt Power Low (Range is 18 to 30 volts). Check and correct voltage. 
Check for additional power-robbing equipment connected to system. May 
require installation of larger VA transformer to be installed in furnace / air 
handler. Clears after fault recovered.
E116 High 24V. 24 Volt Power High (Range is 18 to 30 volts). Check and correct voltage. 
Check for proper line voltage (120V, 240V, etc.) to equipment. Clears when 
control senses proper voltage.
E117 Poor ground detected (Warning only) Provide proper grounding for unit. Check for proper earth ground to the 
system. Warning only will clear 30 seconds after fault recovered.
E120 Unresponsive device. Communication 
only.
Usually caused by delay in outdoor unit responding to indoor unit poling. 
Recycle power. Check all wiring connections. Cleared after unresponsive 
device responds to any inquiry.