Page 28
Once the rst stage prove switch is determined to be open, 
the combustion air inducer is energized on low (rst stage) 
heat  speed.  When  the  dierential  in  the  prove  switch  is 
great enough,  the  prove  switch closes and  a  15-second 
pre-purge begins.
NOTE - During abnormal conditions such as low supply 
voltage or low outdoor temperatures and the low re pres-
sure switch does not close, the combustion air inducer will 
switch to high re. After a 15 second pre-purge the high 
re pressure switch will close and the unit will begin op-
eration  on  high  re.  After  10  to  20  seconds  of  high  re 
operation the unit will switch to low re
After the 15-second pre-purge period, the SureLight
®
 ig-
nitor warms up for 20 seconds after which the gas valve 
opens for a 4-second trial for ignition. The ignitor remains 
energized during the trial until ame is sensed. If ignition 
is not proved during the 4-second period, the control will 
try four more times with an inter purge and warm-up time 
between    trials  of  35  seconds. After  a  total  of  ve  trials 
for ignition (including the initial trial), the control goes into 
Watchguard- Flame Failure mode. After a 60-minute reset 
period, the control will begin the ignition sequence again.
Two Stage Operation / Thermostat Selection DIP 
Switch
The control can be utilized in two modes: SINGLE-STAGE 
thermostat  or  TWO-STAGE  thermostat.  The  thermostat 
selection is made using  a DIP switch and  must be posi-
tioned for the particular application. DIP switch 1, labeled 
T”STAT HEAT STAGE is factory-set in the OFF position for 
use with a two-stage thermostat. Move the DIP switch to 
ON for use with a single stage thermostat.
While  in  the  single-stage  thermostat  mode,  the  burners 
will always re on rst-stage heat. The combustion air in-
ducer  will  operate  on  low  speed  and  indoor  blower  will 
operate on low heat speed. The unit will switch to second 
stage heat after a “recognition  period”.  DIP switch 2, la-
beled SECOND STAGE DELAY, is factory set in the OFF 
position for a 7 minute recognition period. The switch can 
be moved to the ON position for a 12 minute recognition 
period, after which time the unit will switch to second-stage 
heat. While in the two-stage thermostat mode, the burners 
will re on rst-stage heat. The combustion air inducer will 
operate on low speed and  indoor  blower will operate on 
low heat speed. The unit will switch to second-stage heat 
on call from the indoor thermostat. If there is a simultane-
ous call for rst and second stage heat, the unit will re an 
rst stage heat and switch to second stage heat after 30 
seconds  of  operation.  See  Sequence  of  Operation  ow 
charts in the back of this manual for more detail.
TABLE 1 
SureLight
® 
Control 5 Pin Terminal Designation
Pin # Function
1 Ignitor
2 Combustion Air Inducer High 
Speed
3 Combustion Air Inducer Low 
Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
TABLE 2 
SureLight
®
 Control 12 Pin Terminal Designation
Pin # Function
1 Gas Valve Second Stage
2 Second Stage Prove Switch
3 Rollout Switch In
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve First Stage
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Rollout Switch Out
12 First Stage Prove Switch
TABLE 3 
SureLight
® 
Control 6 Pin Terminal Designation
Pin # Function
1 Data Input From Motor
2 Common
3 Not Used
4 Data Output To Motor
5 5 Volt Bias Supply
6 Not Used