Page 39
Ignition Control 107045-XX Diagnostic Modes
Display Action (when button is released)
No change (idle)* Remain in idle mode
Solid “E” Enter diagnostic recall mode
Solid “U” Discharge Air Installed
Solid “F” Enter ame signal mode
Solid “P” (variable speed only) Program unit capacity size (Unit Code)
Two horizontal lines soft disable
*  No  change  implies  the  display  will  continue  to  show 
whatever is currently being displayed for normal operation 
(blinking decimal, active error code, heat state, etc..)
Diagnostic LED
The  seven-segment  diagnostic  LED  displays  operating 
status,  target  airow, error  codes  and  other  information. 
The table beginning on the next page lists diagnostic LED 
codes.
Diagnostic Push Button
The diagnostic push button is located adjacent to the sev-
en-segment diagnostic LED. This button is used to enable 
the  Error  Code  Recall  “E”  mode  and  the  Flame  Signal 
“F” mode. Press the button and hold it to cycle through a 
menu of options. Every ve seconds a new menu item will 
be displayed. When the button is released, the displayed 
item  will  be  selected.  Once  all  items  in  the  menu  have 
been  displayed,  the  menu  resumes  from  the  beginning 
until the button is released.
Error Code Recall Mode
Select  ”E”  from  the  menu  to  access  the  most  recent  10 
error codes. Select “c” from the Error Code Recall menu 
to clear all error codes. Button must be pressed a second 
time  while  “c”  is  ashing  to  conrm  command  to  delete 
codes  Press the button until a solid “≡” is displayed to exit 
the Error Code Recall mode.
Flame Signal Mode
Select ”F” from the menu to access the ame signal mode. 
The integrated control will display the ame current on 7 
segment LED in micro amps (uA).
Flame signal mode is exited after any of the following:
•    Power is reset
•    Pressing  and  holding  push  button  until  3  horizontal 
lines “≡” are displayed
•    10 minutes after entering the ame sense mode. 
Program Unit Capacity/Size Mode
After  the  “P”  is  selected  (by  releasing  the  push  button) 
the integrated control will start ashing the “P” on display 
for 90 seconds. If push button is pressed again and held 
during that time, the control will start to display characters 
corresponding to dierent variable speed furnace models 
for 3 seconds each. While the wanted character-model is 
displayed push button has to be released. Selected option 
will ash display for 10 seconds and during that time push 
button has to be pressed and held for 5 seconds. Once 
control accepts new setting it will store data in non-volatile 
memory  and  reset  itself.  If  10  seconds  expires  or  push 
button is  held  less  than  5  seconds,  control will  exit  eld 
test mode and go into idle without changing programming 
the unit size.
Soft Disable
Soft  disabling  is  when  thermostat  nds  a  device  on  the 
BUS that it does not recognize and the thermostat sends 
a the device a message to be in soft disabling mode until 
properly congured. Two horizontal bars will display.
Steps to follow if the damper control module is displaying
the soft disable code.
1 -    Conrm  proper  wiring  between  all  devices 
(thermostat,  damper  control  module,  indoor  and 
outdoor).
2 -  Cycle power to the control that is displaying the soft 
disable code.
3 -  Put the room thermostat through set up.
4 -  Go to setup / system devices / thermostat / edit / then 
push reset.
5 -  Go to setup / system devices / thermostat / edit / then 
push resetAll.