TABLE 5 Continued 
Ignition Control 103130-XX Diagnostic Codes
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E206 Gas valve second-stage relay failure Furnace will operate on 1st stage for remainder of the 
heating demand. Will clear after fault recovered. If un-
able to operate 2nd stage, replace control.
E207 Hot surface ignitor sensed open. Measure  resistance  of  hot  surface  ignitor.  Replace  if 
open  or  not  within  specied  range  found  in  IOM.  Re-
sumes normal operation after fault is cleared.
E223 Low pressure switch failed open. Check  pressure  (inches  w.c.)  of  low  pressure  switch 
closing on heat call. Measure operating pressure (inch-
es  w.c.).  Inspect  vent  and  combustion  air  inducer  for 
correct operation and  restriction.  Resumes  normal  op-
eration after fault is cleared
E224 Low pressure switch failed closed. Check  operation  of  low  pressure  switch  to  see  if  it  is 
stuck closed on heat call longer than 150 seconds. Mea-
sure operating pressure (inches w.c.). Inspect vent and 
combustion air inducer for correct operation and restric-
tion. Resumes normal operation after fault is cleared.
E225 High pressure switch failed open. Check  pressure  (inches  w.c.)  of  high  pressure  switch 
closing on heat call. Measure operating pressure (inch-
es  w.c.).  Inspect  vent  and  combustion  air  inducer  for 
correct operation and  restriction.  Resumes  normal  op-
eration after fault is cleared.
E226 High pressure switch failed closed Check operation of high pressure switch closing on heat 
call. Measure operating pressure (inches w.c.). Inspect 
vent  and  combustion  air  inducer  for  correct  operation 
and restriction. Resumes normal operation after fault is 
cleared.
E227 Low  pressure  switch  open  during  trial  for  ignition 
or run mode.
Check  pressure  (inches  w.c.)  of  low  pressure  switch 
closing on heat call. Measure operating pressure (inch-
es  w.c.).  Inspect  vent  and  combustion  air  inducer  for 
correct operation and  restriction.  Resumes  normal  op-
eration after fault is cleared.
E228 Combustion air inducer calibration failure Unable  to  perform  pressure  switch  calibration.  Check 
vent  system  and  pressure  switch  wiring  connections. 
Resumes normal operation after fault is cleared.
E229 Ignition on high re IFC switched to high re ignition because low re pres-
sure switch did not close  in  allowed time. No action is 
needed.
E240 Low ame current - Run mode. Check  micro-amperes  of  ame  sensor  using  control 
diagnostics  or  eld-installed  mode.  Clean  or  replace 
sensor. Measure voltage of neutral to ground to ensure 
good unit ground. Alert clears after current heat call has 
been completed.
E241 Flame sensed out of sequence - Flame still pres-
ent.
Shut o gas. Check for gas valve leak. Replace, if nec-
essary. Alert clears when fault is recovered.
E250 Limit switch circuit open. Check for proper ring rate on furnace. Ensure there is 
no blockage in heater. Check for proper air ow. If limit 
not closed within 3 minutes, unit will go into 1-hour soft 
lockout. Resumes normal operation after fault is cleared.
E252 Discharge air temperature too high (gas heat only). Check temperature rise, air ow and input rate. Cleared 
when heat call is nished.
E270 Soft  lockout  -  Exceeded  maximum  number  of  re-
tries. No ame current sensed.
Check for proper gas ow. Ensure that ignitor is lighting 
burner. Check ame sensor current. Clears when heat 
call nishes successfully.