Page 68
 CAUTION
If this unit is being installed in an application with 
combustion air coming in from a space serviced by 
an exhaust fan, power exhaust fan, or other device 
which may create a negative pressure in the space, 
take care when sizing the inlet air opening. The 
inlet air opening must be sized to accommodate the 
maximum volume of exhausted air as well as the 
maximum volume of combustion air required for all 
gas appliances serviced by this space.
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
2
 
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
Roof Terminated
Exhaust Pipe
Furnace
*Intake Debris
Screen
(Provided)
FIGURE 27 
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
2
 
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Furnace
Ventilation
Louvers
(Crawl space)
*Intake Debris Screen Provided)
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
FIGURE 28 
General Guidelines for Vent Terminations
In  Non-Direct  Vent applications,  combustion  air  is  taken 
from indoors or ventilated attic or crawlspace and the ue 
gases are discharged to the outdoors. The EL296UHV is 
then classied as a non-direct vent, Category IV gas fur-
nace.
In Direct Vent applications, combustion air is taken from 
outdoors  and  the  ue  gases  are  discharged  to  the  out-
doors. The EL296UHV is then classied as a direct vent, 
Category IV gas furnace.
In both Non-Direct Vent and Direct Vent applications, the 
vent termination is limited by local building codes. In the 
absence of local codes, refer to the current National Fuel 
Gas Code ANSI Z223-1/NFPA  54  in  U.S.A.,  and current 
CSA-B149 Natural Gas and Propane Installation Codes in 
Canada for details.
Position  termination  according  to  location  given  in  FIG-
URE 30 or FIGURE 31. In addition, position termination so 
it is free from any obstructions and 12” above the average 
snow accumulation.
At vent termination, care must be taken to maintain protec-
tive coatings over building materials (prolonged exposure 
to exhaust condensate  can  destroy protective coatings). 
It is recommended that the exhaust outlet not be located 
within  6  feet  (1.8m)  of  an  outdoor AC  unit  because  the 
condensate can damage the painted coating.
NOTE - See  TABLE  26  for  maximum  allowed  exhaust 
pipe length without insulation in unconditioned space 
during winter design temperatures below 32°F (0°C). If re-
quired exhaust pipe should be insulated with 1/2” (13mm) 
Armaex  or  equivalent.  In  extreme  cold  climate  areas, 
3/4”  (19mm)  Armaex  or  equivalent  may  be  necessary. 
Insulation must be protected from deterioration. Armaex 
with UV protection is permissible. Basements or other en-
closed areas that are not exposed to the outdoor ambient 
temperature and are above 32 degrees F (0°C) are to be 
considered conditioned spaces.
 IMPORTANT
Do  not  use  screens  or  perforated  metal  in  exhaust  or 
intake terminations. Doing so will cause freeze-ups and 
may block the terminations.
 IMPORTANT
For Canadian Installations Only:
In  accordance  to  CSA  International  B149  installation 
codes,  the  minimum  allowed  distance  between  the 
combustion air intake inlet and the exhaust outlet of other 
appliances shall not be less than 12 inches (305mm).