EasyManuals Logo

Lennox EL296UHE Series Unit Information

Lennox EL296UHE Series
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
Page 16
1
2
3
4
5
C
L
G
N
Multi−Meter
(set to VAC)
P48
P49
12
0
12
0
Turn on power to unit. Check for 120 volts across terminals
“Land “Non input plug P48. If voltage is present continue
stream of plug P48 and proceed to test 3.
1
2
3
4
5
C
L
G
N
Multi−Meter
(set to VAC)
P48
P49
24
Switch thermostat to CONTINUOUS FAN MODE. Check for
24 volts across terminal “Con input plug P48and speed tap
used for continuous fan. (1, 2, 3, 4 or 5) on input plug P49. If
24 volts is not present problem may be up stream of plug P49.
Proceed to test 4.
Multi−Meter
(set to VAC)
12
0
12
0
24
Multi−Meter
(set to VAC)
ent, problem is with the harness. If voltage is not present
problem may be may be with the integrated control
Check for 120 volts across terminals “L1” and “Neutralson
the integrated control. If voltage is present, problem is with
the harness. If voltage is not present problem may be may
be with the integrated control.
Test 1
Test 2
Test 3 (if necessary)
Test 4 (if necessary)
FIGURE 8

Other manuals for Lennox EL296UHE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox EL296UHE Series and is the answer not in the manual?

Lennox EL296UHE Series Specifications

General IconGeneral
BrandLennox
ModelEL296UHE Series
CategoryFurnace
LanguageEnglish

Related product manuals