Page 50
VI-MAINTENANCE
 WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could 
result in dangerous operation, serious injury, death 
or property damage.
Improper servicing could result in dangerous 
operation, serious injury, death, or property damage. 
Before servicing, disconnect all electrical power to 
furnace.
When servicing controls, label all wires prior 
to disconnecting. Take care to reconnect wires 
correctly. Verify proper operation after servicing.
At the beginning of each heating season, system should 
be checked as follows by a qualied service technician:
Blower
Check the blower wheel for debris and clean if necessary. 
The blower motors are prelubricated for extended bearing 
life. No further lubrication is needed.
 WARNING
The blower access panel must be securely in place 
when the blower and burners are operating. Gas 
fumes, which could contain carbon monoxide, can 
be drawn into living space resulting in personal 
injury or death.
Filters
All air lters are installed external to the unit. Filters should 
be  inspected  monthly.  Clean  or  replace  the  lters  when 
necessary  to  ensure  proper  furnace  operation. Table  27 
lists recommended lter sizes.
 IMPORTANT
If a higheciency lter is being installed as part of 
this system to ensure better indoor air quality, the 
lter must be properly sized. Higheciency lters
have a higher static pressure drop than 
standardeciency glass/foam lters. If the pressure 
drop is too great, system capacity and performance 
may be reduced. The pressure drop may also cause 
the limit to trip more frequently during the winter and 
the indoor coil to freeze in the summer, resulting in 
an increase in the number of service calls.
Before using any lter with this system,  check the 
specications  provided  by  the  lter  manufacturer 
against the data given in the appropriate Lennox 
Product  Specications  bulletin.  Additional 
information is provided in Service and Application 
Note ACC002 (August 2000).
TABLE 27 
Cabinet Width
Filter Size
Side Return Bottom Return
17-1/2” 16 x 25 x 1(1) 16 x 25 x 1(1)
21” 16 x 25 x 1(1) 20 x 25 x 1 (1)
24-1/2” 16 x 25 x 1(2) 24 x 25 x 1 (1)
Exhaust and air intake pipes
Check  the  exhaust  and  air  intake  pipes  and  all  connec-
tions for tightness and to make sure there is no blockage.
NOTE - After any heavy snow, ice or frozen fog event the 
furnace vent pipes may become restricted. Always check 
the vent system and remove any snow or ice that may be 
obstructing the plastic intake or exhaust pipes.
Electrical
 CAUTION
Failure to use properly sized wiring and circuit 
breaker may result in property damage. Size wiring 
and  circuit  breaker(s)  per  Product  Specications 
bulletin (EHB) and unit rating plate.
1 -  Check all wiring for loose connections.
2 -   Check for the correct voltage at the furnace (furnace 
operating).
3 -   Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
Winterizing and Condensate Trap Care
1 -  1 - Turn o power to the furnace.
2 -   Have  a  shallow  pan  ready  to  empty  condensate 
water.
3 -   Remove the clean out cap from the condensate trap 
and empty water. Inspect the trap then reinstall the 
clean out cap.
Condensate Hose Screens (Figure 56)
Check  the  condensate  hose  screens  for  blockage  and 
clean if necessary.
1 -   Turn o power to the unit.
2 -   Remove  hoses  from  cold  end  header  box.  Twist 
and pull screens to remove.
3 -  Inspect screens and rinse with tap water if needed.
4 -   Reinstall  screens,  reconnect  hoses  and  turn  on 
power to unit.
Hose
Hose
FIGURE 56