Page 38
TABLE 5 Continued
Ignition Control 103130-XX Diagnostic Codes
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E406 LSOM - Compressor open start circuit. Required amount of current is not passing through Start cur-
rent transformer. Clears the error after current is sensed in
START sensor, or after power reset.
E407 LSOM - Compressor open run circuit. Required amount of current is not passing through Run current
transformer. Clears the error after current is sensed in RUN
sensor, or 1 normal compressor run cycle, or after power reset.
E408 LSOM - Compressor contactor is welded. Compressor runs continuously. Clears the error after 1 normal
compressor run cycle or after power reset.
E409 LSOM - Compressor low voltage. Secondary voltage is below 18VAC. After 10 minutes, oper-
ation is discontinued. Clears the code after voltage is higher
than 20 VAC for 2 seconds or after power reset.

Other manuals for Lennox EL296UHV series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox EL296UHV series and is the answer not in the manual?

Lennox EL296UHV series Specifications

General IconGeneral
EfficiencyUp to 96% AFUE
Stages of HeatingTwo-Stage
Blower MotorVariable Speed
Energy Star CertifiedYes
Heat Exchanger WarrantyLimited Lifetime Warranty
Sound LevelQuiet Operation
Fuel TypeNatural Gas
Parts Warranty5-Year Limited Warranty
Heating Capacity44, 000 to 132, 000 BTU/h

Related product manuals