BLOWER DATA
EL296UH110XV60C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
+24% 1385 1965
+18% 1475 1880
+12% 1355 1790
+6% 1370 1725
Factory Default 1200 1630
–6% 1140 1550
–12% 1070 1460
–18% 980 1345
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
Low Medium-Low Medium-High
2
High Low Medium-Low Medium-High
2
High
+ 1060 1245 1345 1545 1560 1740 1930 2125
Factory Default 970 1145 1265 1395 1405 1565 1775 1945
885 1025 1110 1250 1270 1425 1610 1770
BLOWER DATA
EL296UH135XV60D BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
+24% 1770 2125
+18% 1680 2015
+12% 1610 1935
+6% 1485 1855
Factory Default 1440 1740
–6% 1360 1650
–12% 1285 1565
–18% 1215 1460
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
Low Medium-Low Medium-High
2
High Low Medium-Low Medium-High
2
High
+ 1150 1310 1440 1610 1640 1840 2000 2250
Factory Default 1080 1210 1330 1475 1480 1660 1885 2035
985 1095 1210 1315 1330 1500 1675 1885
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control..
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 450 cfm.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 450 cfm.