Page 52
BLOWER DATA
EL296DF045XV36B BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm Second Stage Heating Speed - cfm
+24% 910 1150
+18% 855 1095
+12% 820 1040
+6% 770 990
Factory Default 745 935
–6% 700 880
–12% 665 820
–18% 635 755
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm
Low Medium-Low Medium-High
2
High Low Medium-Low Medium-High
2
High
+ 640 755 850 975 895 1050 1210 1360
Factory Default 580 695 780 880 805 965 1105 1250
– 545 645 720 795 735 865 1000 1130
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specic
DIP Switch Settings.
2
Factory default setting.
NOTES - The eect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, and 38%, of the selected second stage cooling speed - minimum 380 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 380 cfm.