EasyManua.ls Logo

Lennox FLEXAIR FAH 200 - 1.9. INDOOR AIR QUALITY; FILTERS; EC FANS VENTILATION SISTEM

Lennox FLEXAIR FAH 200
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
• 12 •
Application Guide / FLEXAIR-AGU-1505-E
FILTERS
As standard the unit comes with EU3 lters
We can increase the capacity of ltration with an option of G4 and
an option of G4+ F7, to arrive offering an average arrestance of
synthetic dust above 90% (according to EN779:2012).
DOUBLE SKIN PANEL
As an option, indoor unit of FLEXAIR, can be provided by a
double skin panel, to avoid the carrying of insulation particles
inside the building (25mm of thickness).
EC FANS VENTILATION SISTEM
FLEXAIR is tted with EC fans as standard, ensuring that no
belt particles can be carried away into building .This ventilation
system is compliant with EN 13977 air quality norm.
ANALOGUE FILTER DETECTION
Thanks to this sensor, the lter presence and the proper fan
operation is ensured by a pressure drop above the minimum
threshold, and at the same time the lter dirtyness is identi ed
by a pressure drop above the maximum threshold.
REMOVABLE ALUMINIUM DRAIN PAN
All units are equipped with a sloped removable drain pan in
aluminum which can be removed for maintenance, preventing
the growth of bacteria an algae in the drain pan.
1.9. INDOOR AIR QUALITY
1- GENERAL DESCRIPTION
EASY ACCESS TO THE UNIT
COMPONENTS
In FLEXAIR we keep the accessibility of all the components to
the indoor unit, as well as all the internal refrigerant components