BLOWER DATA
G40UH−36A−045 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External
Static
Pressure
High Medium−High Medium−Low Low
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1480 615 1300 545 1100 460 930 385
0.05 1465 605 1290 530 1100 450 930 380
0.10 1445 585 1280 520 1100 445 930 370
0.15 1440 585 1275 505 1095 435 935 365
0.20 1415 570 1260 495 1090 425 935 360
0.25 1400 560 1250 485 1090 420 930 355
0.30 1375 545 1235 470 1075 410 930 350
0.40 1320 520 1195 450 1060 390 915 330
0.50 1265 495 1160 430 1020 375 890 320
0.60 1210 475 1105 410 975 350 840 295
0.70 1135 450 1045 380 910 325 775 280
0.80 1025 415 915 345 810 300 720 265
0.90 885 380 815 320 725 270 640 240
NOTE All air data is measured external to unit with 1 in. cleanable filter (not furnished − field provided) in place. Also see Filter Air Resistance table.
G40UH−36A−070 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External
Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 1500 710 705 1290 610 565 985 465 455 830 390 375
0.05 12 1475 695 695 1275 600 555 980 465 445 820 385 365
0.10 25 1450 685 680 1255 590 545 970 460 440 810 380 360
0.15 37 1425 675 670 1240 585 535 965 455 430 805 380 355
0.20 50 1400 660 655 1225 580 525 955 450 425 795 375 350
0.25 62 1370 645 645 1205 570 510 945 445 415 790 375 345
0.30 75 1340 630 630 1180 555 500 930 440 405 780 370 335
0.40 100 1285 605 610 1140 540 475 900 425 390 745 350 325
0.50 125 1215 575 580 1080 510 450 865 410 375 705 335 310
0.60 150 1150 545 560 1015 480 430 810 380 355 655 310 290
0.70 175 1060 500 535 940 445 405 730 345 330 585 275 270
0.80 200 955 450 515 800 375 370 655 310 305 480 225 260
0.90 225 785 370 475 605 285 325 585 275 270 410 195 255
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished field provided) in place. Also see Filter Air Resistance table.
G40UH−36B−090 PERFORMANCE
External Static
Air Volume / Watts at Various Blower Speeds
External
Static
Pressure
High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 1500 710 720 1255 590 595 1040 490 460 900 425 370
0.05 12 1485 700 705 1250 590 580 1040 490 450 895 420 365
0.10 25 1465 690 685 1240 585 570 1035 490 445 890 420 360
0.15 37 1450 685 675 1235 585 555 1035 490 440 885 420 355
0.20 50 1435 675 660 1225 580 545 1030 485 435 880 415 350
0.25 62 1420 670 645 1215 575 530 1025 485 425 875 415 345
0.30 75 1400 660 630 1200 565 520 1020 480 415 870 410 340
0.40 100 1345 635 595 1170 550 495 1000 470 400 855 405 330
0.50 125 1300 615 575 1135 535 475 965 455 380 830 390 300
0.60 150 1235 585 545 1080 510 445 930 440 360 780 370 290
0.70 175 1165 550 510 1020 480 415 870 410 340 740 350 280
0.80 200 1080 510 480 940 445 385 800 380 315 670 315 260
0.90 225 985 465 445 840 395 355 710 335 290 600 285 245
NOTE All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished field provided) in place. Also see Filter Air Resistance table.