TABLE 6
KGB/KCB120S CAV Blower Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Circuit 1
111 261 114 301 117 343 120 389 122 437 125 489
118 266 121 304 124 349 127 393 131 444 132 496
134 286 138 324 142 366 146 411 149 463 152 518
152 315 155 348 160 390 164 438 169 492 173 547
Circuit 2
111 255 113 293 116 333 118 378 121 427 124 481
118 264 121 299 124 341 126 385 130 434 132 488
134 288 138 324 141 364 144 407 148 458 151 513
152 319 155 352 159 393 164 437 168 488 172 545
120S CAV Blower Charging Curves
60
70
80
90
100
110
120
130
110 120 130 140 150 160 170
Liquid Temperature ( ° F)
Suction Pressure (psig)
Outdoor Temperature (°F)
115°
105°
95°
85°
75°
65°
Circuit 1
Circuit 2