TABLE 6 581125-01
KG/KC 092S Normal Operating Pressures - All-Aluminum Coil
Outdoor Coil Entering Air Temperature
65°F 75°F 85°F 95°F 105°F 115°F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Circuit 1
 247 102   341 108  111 448 113 
106    112 341 116   446 122 
120  124  128 344 132  136 444 140 
 267 141 308 146     447 161 
Circuit 2
 246 118 282 121 322 124 366 127 413 130 464
121   287  327 133 371 136  140 470
132  137  143 336 148 382  430  483
141  148 304  346 161  167 443 173 
092S Charging Curves - All-Aluminum Coil
60
70
80
90
100
110
120
95 105 115 125135 145 155
Liquid Temperature ( F)
Suction Pressure (psig)
Outdoor Temperature (°F)
115°
105°
95°
85°
75°
65°
Circuit 1
Circuit 2
165
130
17
5