Page 1
Corp. 9913−L7
LGA/LGC
LCA/LCC
Service Literature
21 / 30 TON
74 / 105 kW
Revised 01−2009
LGA/LGC/LCA/LCC SERIES
The LGA /LGC/ LCA/LCC 21, 25 and 30 ton (74, 88, 105 kW)
units are configured to order units (CTO) with a wide selection
of factory installed options. The LGA/LGC248H/360H gas/
electric packaged rooftop units are available in 260,000 Btuh,
360,000 Btuh and 480,000 Btuh (76.2 kW, 105.5 and 137.7
kW) heating inputs. Gas heat sections are designed with Len-
nox’ aluminized steel tube heat exchangers. The LCA/
LCC248H/360H cooling packaged rooftop units are
equipped with the same cooling sections as the LGA/
LGC248H/360H units.
LCA/LGA248, LCC/LGC300H and LCC/LGC360H units
may contain a supply air blower equipped with a variable
frequency drive A96 (VFD) which varies supply air CFM. As
duct static increases, the supply air volume will decrease.
As duct static decreases, the supply air volume will in-
crease.
Optional electric heat is factory−or field−installed in LCA /LCC
units. Electric heat operates in single or multiple stages de-
pending on the kW input size. 30kW through 120kW heat
sections are available for the LCA/LCC248H/360H. LGA/
LGC and LCA/LCC units have identical refrigerant circuits
with 21, 25 and 30 ton (74, 88 and 105kW) cooling capaci-
ties. LGA/LCA360H units utilize three compressors, while
the LGA/LCA300H and LGA/LCA248H units utilize four
compressors.
Units are also designed for R−410A refrigerant. See unit
nameplate for refrigerant type and charge. Operating pres-
sures and pressure switch settings are significantly higher
than units charged with R−22. Service equipment for
R−410A units must be rated for R−410A refrigerant.
The LGA and LCA units are designed to accept any of sev-
eral different energy management thermostat control sys-
tems with minimum field wiring. Factory or field provided
control options connect to the unit with jack plugs. When
"plugged in" the controls become an integral part of the unit
wiring.
Information contained in this manual is intended for use by
qulified service technicians only. All specifications are sub-
ject to change. Procedures outlined in this manual are pre-
sented as a recommendation only and do not supersede or
replace local or state codes.
If the unit must be lifted for service, rig unit by attaching four
cables to the holes located in the unit base rail (two holes at
each corner). Refer to the installation instructions for the prop-
er rigging technique.
LGA360
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person-
al injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon-
nect switch(es). Unit may have multiple
power supplies.
Question and Answer IconNeed help?

Do you have a question about the Lennox LGC360H4 and is the answer not in the manual?

Lennox LGC360H4 Specifications

General IconGeneral
ModelLGC360H4
TypeAir Conditioner
RefrigerantR-410A
Voltage208/230V
Phase1
Compressor TypeScroll
Cooling Capacity36000 BTU/h
SEER Rating16 SEER
Sound Level (Outdoor Unit)76 dB

Summary

Unit Specifications

Cooling Performance Data

Detailed specifications for cooling capacity, airflow, and efficiency.

Gas and Electric Heat Specifications

Gas Heat Performance and High Altitude Derates

Gas heat input, efficiency, and high altitude derating factors.

Optional Electric Heat Accessories

Electric Heat Control Modules and Terminal Blocks

Part numbers for electric heat control modules, fuse blocks, and terminal blocks.

Blower Data

Base Unit Blower Resistance and Performance

Static pressure resistance data for base units and blower performance tables.

Unit Components - Control Box Details

Cooling System Components - Compressors and Protection

Compressors and Crankcase Heaters

Information on compressors and their associated crankcase heaters.

Cooling System Components - Ancillary Parts

Gas Heat Components

Optional Electric Heat System Components

Electric Heat Controls, Elements, and Fuses

Components for electric heat, including controls, contactors, limits, and fuse protection.

Installation and Startup Procedures

Pre-Startup Checks and Cooling Initiation

Essential checks before startup and steps for initiating cooling operation.

Refrigerant Charge Verification

Procedures for checking system refrigerant charge using the approach method.

Refrigerant Handling and Charge Verification

R410 A Refrigerant Procedures and Charge Check

Guidelines for R410A refrigerant handling and checking system charge.

Heating System Service Checks

Gas Piping and Pressure Testing Procedures

Procedures for testing gas piping, supply pressure, and manifold pressure.

Wiring Diagrams and Sequences

Sequence of Operation

Heating and Cooling Stage Operation

Detailed sequence of operation for heating and cooling stages, including economizer and blower.