EasyManua.ls Logo

Lennox LGT036

Lennox LGT036
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 46
LGT/LCT036, 048, 060, 072
LCT048
Electric Heat Size 7.5 KW 15 KW
Unit Voltage
208/230V
- 1 Ph
208/230V
- 3 Ph
460V -
3Ph
575V -
3Ph
208/230V -
1 Ph
208/230V
- 3 Ph
460V -
3Ph
575V -
3Ph
Power Exhaust
Option
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
Diagram Key Class
Blower
Type
Amps Amps
F3
RK or K
LS 40 40 25 25 15 15 15 15 40 40 50 50 25 25 20 20
F42
RK or K
LS - - - - - - - - 40 40 - - - - - -
F4
RK or K
1
LS 50 45 35 35 15 15 15 15 50 45 35 35 15 15 15 15
F4
RK or K
1
HS - - 35 30 15 15 15 15 - - 35 30 15 15 15 15
F10
2
CC
LS 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
F27
CC
LS - - - - - - 7.5 7.5 - - - - - - 7.5 7.5
F30
CC
LS 10 10 10 10 5 5 - - 10 10 10 10 5 5 - -
F31
CC
LS - 15 - 15 - 15 - - - 15 - 15 - 15 - -
F57
CC
LS - - - - 3.5 3.5 5 5 - - - - 3.5 3.5 5 5
F57
CC
HS - - - - 10 10 7.5 7.5 - - - - 10 10 7.5 7.5
F61
2
J
LS 60 50 35 35 20 20 15 15 100 90 60 60 30 30 25 25
F61
2
J
HS - - 35 30 20 15 15 15 - - 60 60 30 30 25 25
CB10
3
-
LS 60 50 35 35 20 20 15 15 100 90 60 60 30 30 25 25
CB10
3
-
HS - - 35 30 20 15 15 15 - - 60 60 30 30 25 25
1
When SCCR is installed, F4 fuse is Class J.
2
Fuses F10 and F61 are only used on units with SCCR installed.
3
Units using Circuit Breakers will use CB10 option.