BLOWER DATA
MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT
Electric Heat kW Minimum cfm
7.5 1750
15 2250
22.5 2250
30 2750
45 2750
60 3500
FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE - in. w.g.
Air
Volume
cfm
Wet Indoor Coil Gas Heat Exchanger
Electric
Heat
(LHT)
Econo
mizer
Filters Return
Air
Adaptor
Plate
092, 102
120, 122,
150
Standard
Heat
Medium
Heat
High
Heat
MERV 8 MERV 13 MERV 16
1750 0.04 0.04 0.06 0.02 0.02 0.03 0.05 0.01 0.03 0.06 0.00
2000 0.05 0.05 0.07 0.05 0.06 0.03 0.06 0.01 0.03 0.08 0.00
2250 0.06 0.06 0.07 0.07 0.08 0.04 0.08 0.01 0.04 0.09 0.00
2500 0.07 0.07 0.09 0.10 0.11 0.04 0.11 0.01 0.05 0.10 0.00
2750 0.08 0.08 0.09 0.11 0.12 0.05 0.12 0.02 0.05 0.11 0.00
3000 0.10 0.09 0.11 0.12 0.13 0.06 0.13 0.02 0.06 0.12 0.02
3250 0.11 0.10 0.12 0.15 0.16 0.06 0.15 0.02 0.06 0.13 0.02
3500 0.12 0.11 0.12 0.16 0.17 0.09 0.15 0.03 0.07 0.15 0.04
3750 0.14 0.13 0.14 0.19 0.20 0.09 0.15 0.03 0.08 0.16 0.07
4000 0.15 0.14 0.14 0.21 0.22 0.09 0.19 0.04 0.08 0.17 0.09
4250 0.17 0.15 0.14 0.24 0.28 0.13 0.19 0.04 0.09 0.19 0.11
4500 0.19 0.17 0.15 0.26 0.32 0.14 0.22 0.04 0.09 0.20 0.12
4750 0.20 0.18 0.16 0.29 0.37 0.17 0.25 0.05 0.10 0.21 0.16
5000 0.22 0.20 0.16 0.34 0.43 0.20 0.29 0.06 0.10 0.23 0.18
5250 0.24 0.22 0.16 0.37 0.47 0.22 0.32 0.06 0.11 0.24 0.19
5500 0.25 0.23 0.18 0.44 0.54 0.25 0.34 0.07 0.12 0.25 0.22
5750 0.27 0.25 0.19 0.49 0.59 0.31 0.45 0.07 0.12 0.27 0.25
6000 0.29 0.27 0.20 0.54 0.64 0.33 0.52 0.08 0.13 0.28 0.27