22
Tab.7-11
lParameter table for outdoor unit air volume
NOTE
lShield parts in below tables are standard working conditions for the unit.
Static pressure Pa()Static pressure Pa()
Air flow CFM()Air flow CFM()
For 220V 1N 60Hz
/5 Tons C O Units
Tab.7-12
For 220V 1N 60Hz
/5 Tons H P Units
lCurve diagram of static pressure, air flow volumn
Static pressure
(Pa)
Air flow
(CFM)
Brake
power
(kW)
Fan speed
(rpm)
0 1986 730 1040
10 1978 728 1055
20 1971 725 1070
30 1965 722 1085
40 1956 717 1095
50 1953 711 1105
60 1947 709 1120
-10
0
10
20
30
40
50
60
1,950 1,955 1,960 1,965 1,970 1,975 1,980 1,985 1,990
Static pressure Pa()Static pressure Pa()
Air flow CFM()Air flow CFM()
Air flow CFM()Air flow CFM()
-10
0
10
20
30
40
50
60
1,950 1,955 1,960 1,965 1,970 1,975 1,980 1,985 1,990
Static pressure
(Pa)
Air flow
(CFM)
Brake
power
(kW)
Fan speed
(rpm)
0 1890 538 762
10 1882 515 776
20 1872 500 783
30 1859 489 798
40 1846 475 811
50 1832 463 826
60 1820 450 838
lCurve diagram of static pressure, air flow volumn