19
NOTE
( ) Cooling capacities are rated at 95 amblent,80 entering dry bulb,67 entering wet
bulb.Units are suitableforoperationt2 0%ofnominal CFM.
( )Heating capacities are based on the following conditions:Indoor temperature 68
entering dry bulb, entering dry bulb,outdoor temperature 4 entering dry bulb,4359 5
entering dry bulb.
Tab.7-5
Physical Data( )For Inverter Units
4Tons
Heat Pump
Power voltage/phase/frequency 230V/1/60
Cooling(Btu/h) 48000
Heating(Btu/h) 48000
EER/COP(Btu/h W) 10.0
SEER(Btu/W) 16.0
Length(mm) 1486
Width(mm) 1086
Height(mm) 840
195
199
1490*1070*865
R410A
electronic expansion valve
Compressor Quantity/Type 1/Rotor compressor
Rows 2
Fins per inch 17
Tube diameter(in.) φ7
Rows 4
Fins per inch 17
Tube diameter(mm) φ7
Quantity used/diameter(mm) 1/600
Type Propeller
Drive type direct
Quantity speeds 2
Quantity motors/power(kW) 1/0.23
Motor RPM 1100
Total nominal CFM 4000
Quantity used/diameter(in.) 1/10*10
Type FC centrifugal
Drive type direct
Quantity speeds 2
Quantity motors/power(kW) 1/0.35
Motor RPM 765
Total nominal CFM 1650
Outdoor Static Pressure(Pa) standard(Minimum-Maximum) 0
Indoor Static Pressure(Pa) standard(Minimum-Maximum) 50
Cooling Operation Range °F 63-118
Heating Operation Range °F 19-90
Nominal ton
Model type
Capacity
Performance
Dimensions
Net weigt(Kg)
Outdoor fan
Indoor fan
Gross weight(Kg)
Packing dimension: LxWxH
Refrigerant type
Flow control
Outdoor coil
Indoor coil