Page 31
High Pressure Switch S4 
S4 is  a N.C.  auto-reset high pressure  switch located on 
the  discharge line.  The  switch  shuts  o  the compressor 
when discharge pressure rises above the factory setting. 
The switch on LRP14/16 series units is set to open at 590 
+ 10 psi and close at 418 + 10 psi. S4 is not adjustable. 
Float Switch 
A oat switch is included with the downow kit or can be 
ordered as an accessory (oat switch is factory installed 
on the LRP16 series). The oat switch is designed to pre-
vent condensate water from overowing  the  condensate 
pan due to a restriction in the condensate drain line. The 
oat switch is eld-installed in the condensate drain pan 
near the drain exit (oat switch is factory installed on the 
LRP16 series). Refer to the installation instruction for the 
oat switch kit or the downow kit for location and cutting 
of the red wire located in the blower compartment. 
ELECTRIC HEAT 
Matchups and Ratings 
Matchups  and  ratings  are  listed  with  “ELECTRICAL 
DATA”. 
Electric Heat Components 
See gure 12 for electric heat parts arrangement. 
Limit Switches 1, 2, 3 and 4 
Limit  switches  1,  2,  3  and  4  are  N.C.  auto-reset  high 
temperature limits located on the electric heat vest pan-
el. Each heating element is wired in series with a high 
temperature limit. When the limit opens, the correspond-
ing heating element is de-energized. All other heating 
elements remain energized. The limits will automatically 
close when temperatures return to normal. Limit rating will 
be on front side. 
Heating Element HE1 through HE4 
Heating elements are composed of helix-wound bare ni-
chrome wire exposed directly to the air stream. The ele-
ments are supported by insulators mounted to the wire 
frame. Each element is energized independently by a 
corresponding relay located on the heat vest panel. Once 
energized, heat transfer is instantaneous.
PHK VESTIBULE PARTS ARRANGEMENT
(PHK-10)
SEQUENCER
RELAY
PRIMARY
LIMITS
TB 2
FIGURE 12 
Terminal Strip TB2 PHK-05, -07, -10 
All heating elements require either a second-line voltage 
power source or the use of the single-point power connection 
kit. For electric heat sections without circuit breakers or fus-
es, line voltage connections are made to terminal strip TB2. 
Sequencer Relays 1 and 2 
Relays 1  and 2  are N.O.  sequencer relays  with  a resis-
tive element for a coil and bi-metal disk which actuates 
the contacts. The relays are located on the electric heat 
vest panel and are energized by a 24V heating demand 
(W1 and W2) via jack/plug P2 which is used to connect 
electric heat to the blower control circuit. When energized, 
the internal resistance heats the bi-metal disk causing the 
contacts to close. When the relay is de-energized the disk 
cools and the contacts open. The relays energize dierent 
stages of heat, as well as the blower. The blower is always 
rst on and last o. 
NOTE - As of 2015, all electric heaters must be equipped 
with a second relay to break the line voltage on the return 
side so that a path for the electrical voltage is broken on 
both sides if an element goes to ground. 
Circuit Breaker CB1 and CB2 (option) PHK-15, -20 
Line voltage connections are made to circuit breakers CB1 
and CB2 in electric heat sections with circuit breakers. Ta-
ble 2 shows amp rating for each circuit breaker used. Two-
pole circuit breakers are used.
TABLE 4
Circuit Breakers
UNIT CB1 AMPS CB2 AMPS
PHK15CP 60 AMPS 30 AMPS
PHK20CP 60 AMPS 60 AMPS
GAS HEAT
Gas Valve (GV1) LRP16GE Units
The  LRP16GE  uses  a  gas  valve  manufactured  by 
White-Rodgers. The  valve  is  two-stage  internally  redun-
dant  to  assure  safety  shut  o.  If  the  valve  must  be  re-
placed the same type valve must be used. The valve can 
be converted to LP (see options gas specications for LP 
kit) and is adjustable on both high and low re.
24VAC and gas control knob / switch are located on top 
of the valve. Terminals on the gas valve are connected to 
wires from the ignition control (A3). Inlet and outlet taps 
are located on the valve.
FIGURE 13