Page 21
BLOWER CONTROL BOARD (A54) – LRP16 UNITS
(Setting affects both heat−
ing and cooling modes)
DIAGNOSTIC
LED
HEATING SPEED
SELECTOR PINS
COOLING SPEED
SELECTOR PINS
SELECTOR PINS
ADJUST
FIGURE 9. Blower Control Board (A54) – ECM Motor – LRP16GE / LRP16HP
Blower Control – Units with Constant Torque Motors
LRP14 units that are equipped with constant torque blow-
er motors are energized from the W, G and Y 24 volt ter-
minals from the room thermostat, which are connected to 
the control board in each unit. The constant torque mo-
tor is capable of maintaining a specied CFM throughout 
the external static range. Constant torque units are not 
equipped with a separate blower control.
BLOWER SPEED ADJUSTMENT / OPERATION LRP14 
UNITS
Blower Speeds – Constant Torque Units 
Fan speed on units equipped with constant torque motors 
is eld-adjustable. See blower CFM chart for unit size. 
Blower Speeds — LRP16GE/HP Units 
Fan speed on the HEAT and COOL stage air volume se-
lections are made by jumper pins. 
Continuous Fan Operation 
When the thermostat is set for “Continuous Fan” operation 
and there is no demand for heating or cooling, the blower 
on units with PSC motors will operate at cooling speed. 
On units with constant torque motors, the blower will oper-
ate at low speed with a G call. 
NOTE - With the proper thermostat and sub-base, con-
tinuous  blower  operation is  possible by  closing the  R to 
G  circuit.  Cooling  blower  delay  is  also  functional  in  this 
mode. 
Blower Control Board (A54) LRP16GE/HP Units 
These units are equipped with a variable-speed motor 
which is controlled by a blower control board. See gure 
11. 
On LRP16GE/HP units equipped with ECM motor and a 
two-stage electronic blower control, the indoor blower is 
energized by the ignition control. 
The variable speed motor that is capable of maintaining 
a  specied  CFM  throughout  the  external  static  range. A 
particular  CFM  can  be  obtained  by  positioning  jumpers 
(COOL, HEAT, and ADJUST) on the blower control board. 
The HEAT and COOL jumpers are labeled A, B, C and D. 
Each of the letters corresponds with an air volume (CFM) 
setting. The ADJUST jumper  is labeled  NORM, +,  -  and 
Test. The + and - pin settings are used to add or subtract a 
percentage of the CFM selected. The Test jumper is used 
to operate the motor in the test mode. See gure 11. 
Factory settings for the blower speed jumpers are given in 
the wiring diagram in gure 11. Use the blower data tables 
in this manual to determine the correct air volume for op-
eration in heat and cool mode. 
The CFM LED located on the blower control board ashes 
one time per 100 cfm to indicate selected blower speed. 
For example, if the unit is operating  at  1000 CFM, CFM 
LED will ash 10 times. If the CFM is 1150, CFM LED will 
ash 11 full times plus one fast or half ash.