Page 12
              HEATING COMPONENTS
Gaskets
Collector Box
Orifice Plate
Flue Transition
Pressure Switch
Combustion Air Inducer
Manifold And Gas Valve
Ignitor
Sensor
Rollout Switches
FIGURE 6 
5. Flame Rollout Switches (Figure 6)
Flame  rollout  switch  (S47)  is  a  high  temperature  limit. 
Each furnace is equipped with two identical switches. The 
limit is a N.C. SPST manual-reset limit connected in series 
with the integrated control A92. When S47 senses rollout, 
the integrated control immediately stops ignition and clos-
es the gas valve. If unit is running and ame rollout is de-
tected, the gas valve will close and integrated control will 
be disabled. Rollout can be caused by a blocked heat ex-
changer, blocked ue or lack of combustion air. The switch 
has a factory setpoint of 210°F and cannot be adjusted. 
To manually reset a tripped switch, push the reset button 
located on the control.
6. Primary Limit Control
The primary limit on ML180UHE(X) units is located in the 
heating  vestibule  panel  under  the  combustion  air  induc-
er. See gure 7. When excess heat is sensed in the heat 
exchanger, the limit will open. If the limit is open, the in-
tegrated control energizes the supply air blower and clos-
es the gas valve. The limit automatically resets when unit 
temperature returns to normal.
The switch must reset within three minutes or SureLight®  
control will go into Watchguard for one hour. The switch is 
factory set and cannot be adjusted. The switch may have 
a  dierent  setpoint  for  each  unit  model  number.  If  limit 
switch must be replaced, refer to Lennox ProductZone re-
pair parts list.
Primary Limit Under Combustion Air Inducer
Primary
Limit
FIGURE 7 
7. Flame Sensor (Figure 6)
A ame sensor is located on the left side of the burner sup-
port. The sensor is mounted on the ame rollout plate and 
the tip protrudes into the ame envelope of the left-most 
burner.  The  sensor  can  be  removed  for  service  (clean 
with  steel  wool)  without  removing  any  part  of  the  burn-
ers. During operation, ame is sensed by current passed 
through the ame and sensing electrode. The integrated 
control  allows  the  gas  valve  to  remain  open  as  long  as 
ame signal is sensed.
A microamp DC meter is needed to check the ame signal 
on the integrated control.