EasyManua.ls Logo

Lennox MPB012S4S

Lennox MPB012S4S
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
134
Error Code: EC
Description: LowRefrigerantError
General Note: ThesystemmonitorsthevalueofevaporatorcoilsensorT2fortherst5minutesafterstartup.IfthetemperatureofT2
dropsperthisformulathreetimesintherst5minutesofoperation,thesystemshutsdownandtheerrorcodedisplays.
Forthisformula“Tcool”=theT2temperatureatstartup.
T2<Tcool-3.6°F(2°C)
EC
Poweroffthenrestarttheunitin2min-
utes.
Yes
Yes
ChecktheT2sensor.Is
it functioning
Checktoseeifcoolairisblowingoutof
theindoorairoutlet
No
Yes
ReplacetheindoorPCB
Checkforrefrigerantleaks.
No
Yes
Repairleaksandre-
chargesystem.
Checkforrestrictioninrefrigerantlines.
Clear restriction.

Table of Contents

Related product manuals