EasyManua.ls Logo

Lennox MPB012S4S

Lennox MPB012S4S
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
139
Error Code: F3
Description: Compressordischargetemperaturesensorerror
General Note: Whenthecompressordischargetemperature(T5)ismorethan115°Cfor10seconds,thecompressorwillstopandrestart
tillT5islessthan90°C.
Temperatureprotectionofcompressor.
Checkwhetherthecompressordischargetemp.is
morethan115°C?
No
Checkwhethertheconnectionisrightbetweencom-
pressordischargetemp.sensorandPCBaccordingto
wiringdiagrams?
Checkwhetherthe
refrigerantisleak.
Yes
Stopleakingandadd
refrigerant.
Yes
No
Correctthewiringcon-
nection.
No
Yes
Measuretheresistancevalueofcompressordis-
chargetemp.sensor.Ifthevalueisnotnormalis
normalrefertotheAppendix2?
Replacethecompressor
dischargetemp.sensor.
No
Yes
ReplaceoutdoormainPCB.
No
Replacehighpressurevalveassy.

Table of Contents

Related product manuals