EasyManuals Logo

Lennox MPB012S4S Service Manual

Lennox MPB012S4S
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #147 background imageLoading...
Page #147 background image
147
Error Code: P2
Description: Compressortophightemperatureprotection(OLP)
General Note: Ifthesamplingvoltageisnot5V,theLEDwilldisplaytheP2errorcode.
P2
Checktheairowsystem
of indoor and outdoor units.
Doesaproblemexist?
No
Clearairowblockage.
Yes
Powerofftheunitandwait
10 minutes before restarting.
Yes
Checkcompressor
temperature.Isitwithin
acceptableparameters?
Checktheoverload
protector.Isitproperlywired?
No No
Yes
Measuretheresistance
betweenthetwoportsof
theOLP.Isitzero?
Yes
ReplacetheoutdoorcontrolPCB.
No
ReplacetheOLP.
Ensure a proper connection.
Yes
Error Code: P3
Description: Outdoorunitlowtemperaturelockout.
General Note: Theoutdoorunitwilllockoutifwheninheatingmode,whentheoutdoortemperatureislowerthan-13°F(-25°C)for1hour,
theindoorunitdisplayerrorcode.
Theoutdoorunitwillresumeoperationwheneither:
TheOUTDOORtemperatureishigherthan-7.6°F(-22°C)for10minutesandcompressorhasbeenstoppedfor1hour
or
Outdoortemperatureishigherthan23°F(-5°C)for10minutes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MPB012S4S and is the answer not in the manual?

Lennox MPB012S4S Specifications

General IconGeneral
BrandLennox
ModelMPB012S4S
CategoryAir Conditioner
LanguageEnglish

Related product manuals