EasyManuals Logo

Lennox MWMA012S4-*L User Manual

Lennox MWMA012S4-*L
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #106 background imageLoading...
Page #106 background image
106
Error Code: E3
Description: CommunicationerrorbetweenoutdoorunitmaincontrolandIPM.
General Note: PCBmainchipdoesnotreceivefeedbackfromIPMduring60seconds.
CommunicationmalfunctionbetweenIPM
board and outdoor main board.
IsthereatleastoneLEDintheIPM
boardlight?
No
CheckthesignalwirebetweentheIPM
moduleandthemainboard,isitcon-
nectedcorrectly?
No
Reconnectandretry.Doeserrorstill
display?
Yes
ReplaceIPMboard,andthencheck
whetherthesystemoperatesnormally.
No
Replaceoutdoormainboard,andthen
checkwhetherthesystemoperates
normally.
No
Replacetheelectriccontrolbox.
Problem Solved.
Yes
Yes
No
Yes
Yes
Yes

Table of Contents

Other manuals for Lennox MWMA012S4-*L

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MWMA012S4-*L and is the answer not in the manual?

Lennox MWMA012S4-*L Specifications

General IconGeneral
BrandLennox
ModelMWMA012S4-*L
CategoryAir Conditioner
LanguageEnglish

Related product manuals