EasyManua.ls Logo

Lennox MWMA012S4-*L - Page 121

Lennox MWMA012S4-*L
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
121
Error Code: P3
Description: Outdoorcompressorcurrentoverloadsensed
General Note: Iftheoutdoorcurrentexceedsthecurrentlimitvalue,theLEDwilldisplaythefailure.
Current protection of compressor.
Checkwhethertheinputcurrentofthepower
supplyshouldnotexceedmorethan12Afor18KBTU
units.
For30K,18.5A.
For36K,itis23A.
Yes
CheckwhethertherefrigerantsystemisOK.
Checkwhethertheoutdoorambienttemperature
ishigherthan50°Cor122F
No
Replaceoutdoormainboard.
No
Stoptheunit.
Yes
Checkifoutdoorunithasproperventilation.
No
Correct poor ventilation to outdoor unit.
Yes
Checkoutdoorcoils.Outdoorcoilsshouldbeclean
and free of any debris.
Clean outdoor coils.
Yes
No
Judge5:Therefrigerantpipeisblocked.
Recoverrefrigerantandremoverestriction(s).
Performpropervacuumprocedures,then
restart system.
Yes
No
Replaceoutdoormainboard,andcheckwhetherthe
system can run normally.
No
Replacetheelectriccontrolbox.
Problem Solved.
Yes
Yes

Table of Contents

Other manuals for Lennox MWMA012S4-*L

Related product manuals