EasyManua.ls Logo

Lennox MWMA012S4-*L - Page 132

Lennox MWMA012S4-*L
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
132
Error Code: E4
Description: Indoor return air temperature sensor error.
General Note: Ifthevoltageislowerthan0.06Vorhigherthan4.94V,theLEDwilldisplaytheerror.
Temperaturesensorerror
Checktheconnectionsbetweentempera-
turesensorandPCB.Aretheconnec-
tionsgood?
Yes
No
No
Correcttheconnections
Checktheresistancevalueofthesensor
via Appendix 1 and Appendix 2.
Yes
Replaceindoororout-
doorPCB.
Isitnormal?
No
Replacethesensor.

Table of Contents

Other manuals for Lennox MWMA012S4-*L

Related product manuals