EasyManua.ls Logo

Lennox MWMA012S4-*L - Page 139

Lennox MWMA012S4-*L
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
139
Error Code: F3
Description: Compressordischargetemperaturesensorerror
General Note: Whenthecompressordischargetemperature(T5)ismorethan115°Cfor10seconds,thecompressorwillstopandrestart
tillT5islessthan90°C.
Temperatureprotectionofcompressor.
Checkwhetherthecompressordischargetemp.is
morethan115°C?
No
Checkwhethertheconnectionisrightbetweencom-
pressordischargetemp.sensorandPCBaccordingto
wiringdiagrams?
Checkwhetherthe
refrigerantisleak.
Yes
Stopleakingandadd
refrigerant.
Yes
No
Correctthewiringcon-
nection.
No
Yes
Measuretheresistancevalueofcompressordis-
chargetemp.sensor.Ifthevalueisnotnormalis
normalrefertotheAppendix2?
Replacethecompressor
dischargetemp.sensor.
No
Yes
ReplaceoutdoormainPCB.
No
Replacehighpressurevalveassy.

Table of Contents

Other manuals for Lennox MWMA012S4-*L

Related product manuals