EasyManua.ls Logo

Lennox MWMA012S4-*L - Page 150

Lennox MWMA012S4-*L
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
150
Error Code: P6 (continued)
LowPressureConnection
Isthewiringbetweenthelowpressureswitchand
main control board is connected properly.
Yes
Isthelowpressureprotectorbroken?
Method:Disconnecttheplug.Measuretheresistance
ofthelowpressureprotector,iftheprotectorisnormal
thevalueis0.
Yes
Connect it properly..
No
Replacelowpressureprotector.
No
Checkwhethertheoutdoorambienttemperatureisto
low.
No
Stoptheunit.
Yes
Checkwhetherthehighpressurevalveisopened.
Yes
Fullyopenthehighpressurevalve.
No
Checkiftheindoorfanrunsproperlyincoolingmode.
Refertothesolutionoffanspeedmal-
function(E8).Findoutthecausecorrect
it.
No
Yes
Replaceoutdoormainboard.
No
Refrigerantisnotenough.Addtherefrigerant.

Table of Contents

Other manuals for Lennox MWMA012S4-*L

Related product manuals