EasyManua.ls Logo

Lennox WA Series

Lennox WA Series
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation - Operation - Maintenance manual (IOM) AIR COOLED CHILLERS & SPLIT UNITS - 1106-E • 55 •
WA STANDARD
WA
075
090
100
110
130
150
Operating limits for evaporator
Water
Test pressure
bar
10
Refrigerant
Test pressure
bar
29
Water
Max. operating pressure
bar
6
Refrigerant
Max. operating pressure
bar
29
Water
Minimum flow rate
m
3
/h
8°C
T
Water
Maximum flow rate
m
3
/h
3°C
T
Operating limits for evaporator
Safety
Low pressure cut out
bar
0,7
Safety
Interlocking of low pressure
bar
2,2
Safety
High pressure cut out
bar
29
Safety
High pressure reset
bar
20
WA
200
230
270
300
370
Operating limits for evaporator
Water
Test pressure
bar
10
Refrigerant
Test pressure
bar
29
Water
Max. operating pressure
bar
6
Refrigerant
Max. operating pressure
bar
29
Water
Minimum flow rate
m
3
/h
8°C
T
Water
Maximum flow rate
m
3
/h
3°C
T
Operating limits for evaporator
Safety
Low pressure cut out
bar
0,7
Safety
Interlocking of low pressure
bar
2,2
Safety
High pressure cut out
bar
29
Safety
High pressure reset
bar
20

Related product manuals