EasyManuals Logo

Lennox ZCC Series User Manual

Lennox ZCC Series
49 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
Page 36
A6 Enthalpy Control LED’S

is suitable for free cooling. When an optional IAQ sensor
        
IAQ reading is higher than setpoint requiring more fresh

A6 ENTHALPY CONTROLLER
A
B
C
D
Open
Min
Pos
FREE COOLING SETPOINT;
A=Completely counterclockwise
D=Completely clockwise
OUTDOOR AIR
SUITABLE LED
Free
Cool
DCV
EXH
EXH
Set
2V 10V
DCV
Max
2V 10V
DCV
Set
2V 10V
IAQ SETPOINT
IAQ READING IS
ABOVE SETPOINT
MUM POSITION
IAQ MAXIMUM
POSITION
(set higher than
minimum position)
FIGURE 20
Free Cooling Setpoint
Outdoor air is considered suitable when temperature and
humidity are less than the free cooling setpoints shown






󰀨
A6 enthalpy control free cooling setpoint potentiometer

TABLE 9
ENTHALPY CONTROL SETPOINTS
Control Setting 
A 
B 
C 
D 
Damper Minimum Position
NOTE - A jumper is factory-installed between TB1 R and
OC terminals to maintain occupied status (allowing min-
imum fresh air). When using an electronic thermostat or
energy management system with an occupied/unoccu-
pied feature, remove jumper.
1 - Set thermostat to occupied mode if the feature is
available. Make sure jumper is in place between

does not have the feature.
2 - 
desired fresh air percentage.
Note - Damper minimum position can be set lower
than traditional minimum air requirements when
an IAQ sensor is specied. Dampers will open to
DCV MAX setting (if CO2 is above setpoint) to meet
traditional ventilation requirements.
3 - Measure outdoor air temperature. Mark the point on
          

4 - Measure return air temperature. Mark that point on


       
temperature. Mark that point on the top line of chart

6 - Draw a straight line between points A and B.
7 - Draw a vertical line through point C.
8 - Draw a horizontal line where the two lines meet.

     
MIN POS SET potentiometer higher. If fresh air


until calculation reads desired fresh air percentage

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox ZCC Series and is the answer not in the manual?

Lennox ZCC Series Specifications

General IconGeneral
BrandLennox
ModelZCC Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals