In shared IO mode, there are power issue related to primary node, i.e., the primary node reports plannar
power fault, or the primary node has been removed unexpectedly, thus the mellanox CX-5 card has no
function, and the power permission of both primary node and auxilary node will be denied.
Severity: Critical
User Action:
1. Insert the primary node if it has been remove unexpectedly
2. Reseat the primary node if it has report planar power fault
3. Check the SEL if the SEL be deasserted
2107023E: NODE4_PWRNOREADY: Slot Or Connector, transition to Critical from less severe was
asserted.
In shared IO mode, the primary node does not turn on its PIOR power, thus the mellanox CX-5 card has
no function, and the power permission of both primary node and auxilary node will be denied.
Severity: Critical
User Action:
1. Reset the XCC of the primary node
2. Reseat the primary node
2107023F: NODE4_PWRFAULT: Slot Or Connector, transition to Critical from less severe was
asserted.
In shared IO mode, there are power issue related to primary node, i.e., the primary node reports plannar
power fault, or the primary node has been removed unexpectedly, thus the mellanox CX-5 card has no
function, and the power permission of both primary node and auxilary node will be denied.
Severity: Critical
User Action:
1. Insert the primary node if it has been remove unexpectedly
2. Reseat the primary node if it has report planar power fault
3. Check the SEL if the SEL be deasserted
21070668: NODE1_FS_NORESP: Slot Or Connector, transition to Non-recoverable was asserted.
The BMC has no response over 7 minutes after the client OS is power on, no further action will be taken.
Severity: Critical
User Action:
1. Please shutdown the OS
2. Reset the XCC
3. Check the SEL if other Fail-Safe SEL asserted
21070669: NODE2_FS_NORESP: Slot Or Connector, transition to Non-recoverable was asserted.
The BMC has no response over 7 minutes after the client OS is power on, no further action will be taken.
Severity: Critical
User Action:
1. Please shutdown the OS
2. Reset the XCC
3. Check the SEL if other Fail-Safe SEL asserted